Chapter 12 Description of Parameter SettingsMS300 (High Speed Model)
12-03-15
AFM Output Bias
Factory Setting: 0.00
Settings -100.00~100.00 %
Example 1, AFM 0~10V is set output frequency, the output equation is
27-03 10V 24-03 )
00-01
FrequencyOutput
(10V
Example 2, AFM 0~20 mA is set output frequency, the output equation is
27-0320mA 24-03 )
00-01
FrequencyOutput
(20mA
Example 3, AFM 4~20 mA is set output frequency, the output equation is
27-0316mA 24-03 )
00-01
FrequencyOutput
(16mA4mA
This parameter can set the corresponding voltage of analog output 0.
AVI Terminal Input Selection
Factory Setting: 0
Settings 0: 0~10 V
3: -10 V ~ +10 V (Pr. 03-69 ~ 03-74 is valid)
ACI Terminal Input Selection
Factory Setting: 0
Settings 0: 4~20 mA
1: 0~10 V
2: 0~20 mA
When changing the input mode, please check if the switch position of external terminal (ACI) is
correct or not.
Status of PLC Analog Output Terminal
Factory Setting: Read only
Settings Monitor the status of PLC analog output terminals
bit 1: AFM
bit 2: AO10
bit 3: AO11
P. 03-30 shows the external multi-function output terminal that used by PLC.
AFM 1
10325476
NOTE
2 =128 2 =64
2=32 2
4
=16 2 =8
2