95-876882.1
2. Resistor leads should be cut to a length of
approximately 1 1/2 inches (40 mm).
3. Bend the leads and install the resistors as
shown in Figure 6.
4. Maintain a 3/8 inch (10 mm) minimum gap
between the resistor body and the terminal
block or any other neighboring parts.
NOTE
The resistors can only be used within the
flameproof (Ex d) terminal compartment.
Unused conduit entries shall be closed with
suitable blanking elements.
B2254
FIRE ALARM PANEL
X3302 DETECTOR
ALARM
24 VDC
+
–
WIRING NOTES:
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL o
i
TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.
E.O.L.
DEVICE
4
o
i
TEST
3
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
COM FIRE
2
COM FIRE
N.O. FIRE
2
N.O. FIRE
N.C. FIRE
2
N.C. FIRE
COM FAULT
1
COM FAULT
N.O. FAULT
1
N.O. FAULT
+Vin
+Vin
–Vin
–Vin
–Vin
29
28
27
26
25
24
23
22
21
SPARE
SPARE
RS-485 A
RS-485 B
MAN O
i
mA +
mA –
mA + REF mA – REF
COM AUX
N.O. AUX
N.C. AUX
Figure4—X3302 Terminal Block
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
mA +
mA –
mA + REF
mA – REF
COM FIRE
COM FIRE
N.O. FIRE
N.O. FIRE
N.C. FIRE
N.C. FIRE
COM FAULT
COM FAULT
N.O. FAULT
N.O. FAULT
+Vin
+Vin
–Vin
–Vin
–Vin
29
28
27
26
25
24
23
22
21
SPARE
SPARE
COM AUX
N.O. AUX
N.C. AUX
RS-485 A
RS-485 B
MAN O
i
Figure5—X3302 Wiring Terminal Identication
3/8 INCH (10 MM) GAP MINIMUM
1112
13
141516171819
B2126
BULKHEAD
Figure6—Resistor Installation (For Ex d Wiring only)
Figure7—Ex d Wiring Option