95-8768152.1
4. Recalibrate the detector's o
i
system. Refer
to the Enhanced Flame Inspector manual,
number 95-8751, for instructions regarding
o
i
reflector plate replacement and o
i
system
recalibration.
IMPORTANT
If the
o
i
reector plate is replaced, you must
recalibrate the
o
i
system.
Recalibration of the o
i
system requires the
use of the Inspector Connector and Enhanced
Flame Inspector Software. These two items are
included in the o
i
replacement kit, or they can be
purchased separately. See "Ordering Information"
for details. The o
i
system may also be recalibrated
using HART or Modbus on models that are so
equipped.
X3302 o
i
Reector Plates
X3302 models are supplied with either a black or
a stainless steel o
i
reflector plate. These plates
are not interchangeable. Order the replacement
that matches the o
i
reflector plate on your X3302
Flame Detector.
PERIODIC CHECKOUT PROCEDURE
In compliance with SIL 2, a checkout of the
system using the Mag o
i
or Man o
i
feature
should be performed regularly to ensure that
the system is operating properly. Refer to Table
1 in the X3302 Safety manual, number 95-8720,
for frequency of proof tests. To test the system,
perform the “Fire Alarm Test” as described in the
“Startup Procedure” section of this manual.
CLOCK BATTERY
The real time clock has a backup battery that will
operate the clock with no external power. Return
the device to the factory for battery replacement
if needed.
NOTE
If the backup battery is depleted, there is no
effect on the operation of the ame detector,
but the time stamping of the data log may
be affected.
FEATURES
• Unequaled false alarm rejection
• Responds to a fire in the presence of
modulated blackbody radiation (i.e., heaters,
ovens, turbines) without false alarm
• Microprocessor controlled heated optics for
increased resistance to moisture and ice
• Automatic, manual or magnetic o
i
testing
• Easily replaceable o
i
reflector plate
• Fire, fault and auxiliary relays standard
• 0–20 mA isolated output (optional)
• Eagle Quantum Premier
®
LON/SLC output
(optional)
• Sustained Fire Mode (optional)
• HART communication (optional)
• FDT/DTM capable
• Multiple sensitivity levels
• A tri-color LED on the detector faceplate
indicates normal condition and notifies
personnel of fire alarm or fault conditions
• Operates under adverse weather conditions
and in dirty environments
• Mounting arm allows easy sighting
• Integral wiring compartment for ease of
installation
• Explosion-proof/flame-proof detector housing.
Meets FM, CSA, ATEX Directive and IECEx
certification requirements
• Class A wiring per NFPA-72
• 5 year warranty
• RFI and EMC Directive compliant
Associated Manuals
TITLE FORM NUMBER
Pulse 95-8779
EQP
95-8533
SIL 2 (Safety)
95-8720
HART Addendum
95-8613
Q9033 Mounting Arm
and Collar Attachment
95-8686
Enhanced Flame Inspector
Software for X-Series Flame Detectors
95-8751
Q1130 Flange Mount 95-8662