24 95-87682.1
APPENDIX A
FM APPROVAL AND PERFORMANCE REPORT
THE FOLLOWING ITEMS, FUNCTIONS, AND OPTIONS DESCRIBE THE FM APPROVAL:
Explosion-proof for Class I, Div. 1, Groups B, C and D (T4A) Hazardous (Classified) Locations per FM 3615.
Dust-ignition proof for Class II/III, Div. 1, Groups E, F and G (T4A) Hazardous (Classified) Locations per FM 3615.
Nonincendive for Class I, Div. 2, Groups A, B, C and D (T3C) Hazardous (Classified) Locations per FM 3611.
Nonincendive for Class II, Div. 2, Groups F and G (T3C) Hazardous (Classified) Locations per FM 3611.
Enclosure rating NEMA/Type 4X per NEMA 250.
Ambient Temperature Limits: –40°F to +167°F (–40°C to +75°C).
Automatic Fire Alarm Signaling Performance verified per FM 3260 (2018).
Flameproof per ANSI/ISA 60079-0, -1, -7, -31
Class I, Zone 1, AEx db eb IIC T6...T5
T6 (Tamb –40°C to +60°C)
T5 (Tamb –40°C to +75°C)
Zone 21, AEx tb IIIC T130°C
Tamb –40°C to +75°C
IP66
Class I, Zone 1, AEx db IIC T6...T5
T6 (Tamb –40°C to +60°C)
T5 (Tamb –40°C to +75°C)
IP66/IP67
The following accessories are FM approved for use with the X3302 Flame Detector:
Part Number
Description
102740-002
Magnet
007739-001
Magnet and Extension Pole
010857-001 Q1130A1001 Flange Mount Assembly
007290-001
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
007290-002
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
011385-001
Q9033 Collar Attachment
Special conditions for safe use:
The front window assembly contains a special cemented joint construction. In accordance with
ANSI/ISA 60079-1 clause 5.1.c, all inspections, repair and/or adjustments to this front window
assembly shall be done by Detector Electronics Corporation only.
The EOL resistor can only be used within the flameproof terminal compartment.
EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power
dissipation not to exceed 2.5 watts.
The Multispectrum infrared (IR) flame detector type X3302 is to be installed in places where there
is a low risk of mechanical damage.
See the “Maintenance” section of this manual for guidance on minimizing the risk from electrostatic discharge.
Flameproof joints are not intended to be repaired. See the “Device Repair and Return” section of
this manual for more information on conducting repairs.
The following performance criteria were verified:
AUTOMATIC OPTICAL INTEGRITY TEST:
The detector generated an optical fault in the presence of contamination on any single or combination
of lens surfaces resulting in a loss of approximately 50% of its detection range, verifying that the
detector performs a calibrated Automatic o
i
test for each sensor. Upon removal of the contamination,
the detector fault was cleared and the detector was verified to detect a fire.