EasyManua.ls Logo

Detcon IR-700 - Page 32

Detcon IR-700
50 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Model IR-700
IR-700 Instruction Manual Rev. 4.3 Page 28 of 46
Zero Fault
If the sensor drifts below 10% LEL, the “Zero Fault” will be declared. A “Zero Fault” will cause a “Fault
Detected” message to scroll once a minute on the ITM display and drop the 4-20mA output to 0mA. The
Modbus™ fault register bit for Zero Fault will be set and will not clear until the fault condition has been cleared.
The sensor should be considered “Out-of-Service” until a successful AutoZero calibration is performed.
Range Fault AutoSpan
If the sensor fails the minimum signal change criteria during AutoSpan sequence (Section 3.4.2) the “Range
Fault” will be declared. A “Range Fault” will cause a “Fault Detected” message to scroll once a minute on the
ITM display and drop the 4-20mA output to 0mA. The Modbus™ fault register bit for Range Fault will be set
and will not clear until the fault condition has been cleared. The sensor should be considered “Out-of-Service”
until a successful AutoSpan calibration is performed.
Stability Fault AutoSpan
If the sensor fails the signal stability criteria during AutoSpan sequence (Section 3.4.2) the “Stability Fault” will
be declared. A “Stability Fault” will cause a “Fault Detected” message to scroll once a minute on the ITM
display and drop the milliamp output to 0mA. The Modbus™ fault register bit for Stability Fault will be set and
will not clear until the fault condition has been cleared. The sensor should be considered as “Out-of-Service”
until a successful AutoSpan calibration is performed.
Clearing Fault AutoSpan
If the sensor fails the signal stability criteria during AutoSpan sequence (Section 3.4.2) the “Clearing Fault” will
be declared. A “Clearing Fault” will cause a “Fault Detected” message to scroll once a minute on the ITM
display and drop the milliamp output to 0mA. The Modbus™ fault register bit for Clearing Fault will be set and
will not clear until the fault condition has been cleared. The sensor should be considered as “Out-of-Service”
until a successful AutoSpan calibration is performed.
Sensor Fault
If the plug-in IR sensor, or the supporting electronics, fails to meet the required minimum or maximum working
signal parameters a “Sensor Fault” will be declared. A “Sensor Fault” will cause a “Fault Detected” message to
scroll once a minute on the ITM display. The Modbus™ fault register bit for Sensor Fault will be set and will
not clear until the fault condition has been cleared. If a Sensor Fault occurs, the 4-20mA signal will be set at
0mA until the fault condition is resolved.
Processor Fault
If the detector has any unrecoverable run-time errors, a “Processor Fault” is declared. A “Processor Fault” will
cause a “Fault Detected” message to scroll once a minute on the ITM display. The Modbus™ fault register bit
for Processor Fault will be set and will not clear until the fault condition has been cleared. If a Processor Fault
occurs, the 4-20mA signal will be set at 0mA until the fault condition is resolved.
Memory Fault
If the detector has a failure in saving new data to memory, a “Memory Fault” is declared. A “Memory Fault”
will cause the “Fault Detected” message to scroll once a minute on the ITM display. The Modbus™ fault register
bit for Memory Fault will be set and will not clear until the fault condition has been cleared. If a Memory Fault
occurs, the 4-20mA signal will be set at 0mA until the fault condition is resolved.

Table of Contents

Related product manuals