www.dimplex.de 452172.66.10-EN · FD 0311 EN-43
LIA 0608BWCF M - LIA 1316BWCF M English
Information requirements for heat pump space heaters and heat pump combination heaters
Item Symbol Value Unit Item Symbol Value
Unit
Tj = - 7°C
Pdh
10,69 kW Tj = - 7°C
COPd
2,01 -
Tj = + 2°C
Pdh
6,86 kW Tj = + 2°C
COPd
3,43 -
Tj = + 7°C
Pdh
4,64 kW Tj = + 7°C
COPd
4,66 -
Tj = + 12°C
Pdh
3,32 kW Tj = + 12°C
COPd
6,13 -
Tj = bivalent temperature
Pdh
10,69 kW Tj = bivalent temperature
COPd
2,01 -
Tj = operation limit temperature
Pdh
9,19 kW Tj = operation limit temperature
COPd
1,76 -
For air-to-water heat pumps
For air-to-water heat pumps:
Tj = -15°C (if TOL < -20°C)
Pdh
/ kW Tj = -15°C (if TOL < -20°C)
COPd
/-
Bivalent temperature
T
biv
-7 °C
For air-to-water heat pumps:
Operation limit temperature
TOL -10 °C
Cycling interval capacity for heating
Pcych
-kW
Cycling interval efficiency COPcyc
--
Degradation co-efficient (**)
Cdh
0,9 -
Heating water operating limit
temperature
WTOL 65 °C
Power consumption in modes other than active mode
Supplementary heater
Off mode
P
OFF
0,014
kW Rated heat output (*)
Psup
2,91 kW
Thermostat-off mode
P
TO
0,024
kW
Type of energy input
eletrical
Standby mode
P
SB
0,014
kW
Crankcase heater mode
P
CK
0,000
kW
Other items
Capacity control
variable
- 4060
m³ /h
Sound power level, indoors/ outdoors
L
WA
43/65 dB - --
m³ /h
Emissions of nitrogen oxides
NO
x
-
mg/kWh
Declared load profile
XL
Water heating energy efficiency
η
wh
105 %
Daily electricity consumption
Q
elec
7,55 kWh Daily fuel consumption
Q
fuel
-
kWh
Contact details
(**) If Cdh is not determined by measurement nthen the default degradation is Cdh = 0,9
(--) not applicable
Model
Dimplex LIA 1316BWCF (LIA 1316 + LIA BW14)
Air-to-water heat pump
yes
Water-to-water heat pump
no
Brine-to-water heat pump
no
Low-temperature heat pump
no
Equipped with a supplementary heater
yes
136
%
Heat pump combination heater
no
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low- temperature heat pumps, parameters
shall be declared for low-temperature application.
Rated heat output (*)
Prated
12,08
kW
Seasonal space heating energy
efficiency
η
s
Parameters shall be declared for average climate conditions:
For air-to-water heat pumps: Rated
air flow rate, outdoors
For water-/brine-to-water heat
pumps: Rated brine or water flow
rate, outdoor heat exchanger
Declared capacity for heating foer part load at indoor temperature 20°C and
outdoor temperature Tj
Declared coefficient of performance or primary energy ratio for part load at
indoor temperature 20 °C and outdoor temperature Tj
For heat pump combination heater:
Glen Dimplex Deutschland GmbH, Am Goldenen Feld 18, 95326 Kulmbach
(*) For heat pump space heaters and heat pump combination heaters, the rated output Prated is equal to the design load for heating Pdesignh , and the rated
heat output of a supplementary capacity for heating sup(Tj ).