EasyManua.ls Logo

DISCOVER ELEMENT - Charging Profile Setup

Default Icon
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28
NOTICE
The battery module must be charged within 24 hours if discharged below 10% SOC.
Otherwise, irreversible damage to the battery module cells will occur in a very short
period of time and void the warranty.
NOTE
When the 48-48-5120-H battery cells are between -20°C (-4°F) and 5°C (41°F) and
connected to a charging source, energy is diverted from the charging source to the
internal heater until the battery cells reach 8°C (46.4°F). If the BMS triggered the Under-
temperature in Charge protection, the battery module will not allow charging until the
cell temperature is 2°C (36°F).
10.4 Charging Profile
When using open-loop charging, the Power Conversion device will require setting
up a charging profile. Using the controller of the Power Conversion device, set up
a charging configuration with a Lithium charge profile that matches the charge and
discharge settings. Refer to Table 3-1, ELEMENT ESS Electrical Specifications for
charging parameters.
Refer to the appropriate Application Note from www.discoverbattery.com for setting
up closed-loop parameters and integrating inverter-chargers and battery chargers.
100%SOC
Bulk Absorption Float
U1 Max
Absorption & Balancing
CURRENT
VOLTAGE
U2 Float
Bulk Vdc
I Max
I Min
Terminate at 2%-3% of
battery rated capacity
200 milliamps required for
balancing current
Figure 10. Charge Graph
NOTICE
Charge with a Lithium charge profile matching the specifications for the ELEMENT
ESS battery module.
Do not charge using a lead-acid charging profile. Charging using a lead-acid profile
will void the warranty.