Disposal VARC Chiller Controls
8.2 Envelope Zone Status
Descriptions
Refer to the following table for envelope alarms. The
alarm shows the zone number and the description
provides details.
Zone Name Description
1 Inside envelope
zone
Working point inside limits
2 High compression
ratio
Low gas density ->
maximum discharge
temperature
3 High condensing
pressure
Mechanical limit
4 Maximum motor
current
High gas density->
maximum torque
5 High evaporating
pressure
High gas density->
mechanical limit, noise
6 Low compression
ratio
Loss of contact between
spirals, vibrations
7 Low pressure
difference
Loss of lubrication
8 Low condensing
pressure
Low oil temperature ->
high viscosity -> poor
lubrication
9 Low evaporating
pressure
Low gas density -> low
motor cooling
9 Disposal
M
Place the packaging material in the appropriate
recycling waste bins, whenever possible. Consult
a local recycling center or specialist dealer for
details about how to dispose of the product in
accordance with all applicable national and local
regulations.
10 Warranty Information
LIMITED WARRANTY AVAILABLE AT
WWW.DOMETIC.COM/WARRANTY.
IF YOU HAVE QUESTIONS, OR TO OBTAIN A COPY
OF THE LIMITED WARRANTY FREE OF CHARGE,
CONTACT:
DOMETIC CORPORATION
MARINE CUSTOMER SUPPORT CENTER
2000 NORTH ANDREWS AVENUE
POMPANO BEACH, FLORIDA, USA 33069
1-800-542-2477

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dometic PGD1 and is the answer not in the manual?

Dometic PGD1 Specifications

General IconGeneral
BrandDometic
ModelPGD1
CategoryControl Unit
LanguageEnglish

Related product manuals