Evolution FDX
18
15 BOILER DELIVERY
The Technical Assistance Service, once the first start-up has been carried out, will explain the
boiler operation to the users by informing them about the most necessary remarks.
The installer will be responsible for explaining to the users the operation of any control or
regulation device that is a part of the installation and it is not supplied with the boiler.
16 BOILER MAINTENANCE
In order to maintain the boiler under correct operating conditions, a checking operation is to be
made by DOMUSA’s authorised personnel on a yearly basis.
16.1 Boiler cleaning
To maintain the boiler under correct operating conditions, it is recommended to carry out one
annual clean-up of the combustion chamber, flue gases pipes and condensator. For it, with
the boiler, it is supplied an appropriate brush of clean-up. This brush is located in the front
side of the boiler, near door.
The combustion chamber and flue gases pipes should not be cleaned with chemical
products or steel hard brushes. It should put on special care after all the operations of
clean-up, making several power on cycles, checking the correct operation of all the
components.
For a correct clean-up, follow the following recommendations carefully:
Boiler corp cleaning
- Open and extract the outside door of the boiler.
- Dismount the burner (4), unscrewing the female screw located in the upper side of
burner.
- Dismount the combustion chamber door and flue gases tap, unscrewing the six female
secrews located around them.
- Clean the flue gases pipes of cast iron corp with the cleaning brush supplied with the
boiler.
- Clean the combustion chamber of the boiler.
- Once concluded these operations of clean-up, mount the combustion chamber door, the
flue gasees tap, the burner and the external door of the boiler.
Condensator cleaning
- Open and retract the external top cover of the boiler, to access to the condensator,
located in the back side of the cast iron body.
- Open the upper cover of the condensator, to access to the flue gases pipes of it. To open
this cover, first turn on their shaft until the slots of the closing "clip" coincide in the
external part of the cover (see picture), once turned the cover, extract it.
- Extract the smoke turbulators located inside the condensator.
- Clean the condensator with the cleaning brush supplied with the boiler.