Book: 23227143 (8-24-2010) Rev CPage46
COMPRESSOR CODE 32
RT2, Airend Discharge Temperature Sensor Fault
RT2 Temperature Sensor Circuit:
Circuit Description:
The temperature sensor connects to the WEDGE controller as shown in the
circuit above. RT2 is a 10K ohm Thermistor type temperature sensor. The yellow
WJDe is the sense line to the WEDGE. The brown WJDe is the sensor ground.
Component Location:
RT2 temperature sensor is located in the discharge port of the airend.
Explanation:
The WEDGE has detected an out of range reading from the RT2 temperature
sensor.
Effect:
Code 32 is a SHUTDOWN condition and will stop the machine. The Compressor
Malfunction light will be on solid, and Code 32 will be displayed.