COMPRESSOR CODE 53
RT1, Separator Tank Temperature Sensor Fault
RT1 Temperature Sensor Circuit:
Circuit Description:
The temperature sensor connects to the WEDGE controller as shown in the
circuit above. RT1 is a 10K ohm Thermistor type temperature sensor. The yellow
WJDe is the sense line to the WEDGE. The brown WJDe is the sensor ground.
Component Location:
RT1 temperature sensor is located on the side of the separator tank near the
safety valve.
Explanation:
The WEDGE has detected an out of range reading from the RT1 temperature
sensor.
Effect:
Code 53 is a SHUTDOWN condition and will stop the machine. The Compressor
Malfunction light will be on solid, and Code 53 will be displayed.