11 Error messages
Display Display
LED
Meaning/cause Troubleshooting
In 01 none Blockage
The door is blocked due to an obstacle and the
door movement was stopped by the
drive unit.
The door movement should be tested in a deenergized
state and a possibly existing stiffness must be
eliminated. The permanent operation of a defective
door may damage the drive unit. A blocking is also
often triggered by people. The reason for this might be
that the detection range of the sensors is not suitable
for the drive unit and that the door will inevitably be
touched during the passage. In this case, the detection
range of the sensors and/or the opening speed of the
drive unit should be increased. The effectiveness is to be
verified by passing through the door.
In 08 none Shutdown drive function
The contact 4/4a is opened. The drive unit
switches into the emergency mode and
only a manual passage is possible.
An emergency command mechanism, a door lock switch
or other safety system may be connected to the input.
Either the system has actually triggered or there is a
defect. The activation must be reset.
The drive unit starts the operation automatically. If
this is not the case, the wiring and the causing systems
must be tested.
In 09 none Upgrade Card signal error
The installed Upgrade Card was removed or the
initially installed Upgrade Card
(container module) had not been inserted
during the installation of 2 Upgrade Cards.
Installed Upgrade Cards must remain permanently in
the control unit and must not be removed. If several
Upgrade Cards are installed, the Upgrade Card used
first has the function of a container module and must
be the last one to be attached to the control unit
(see chapter Upgrade Card).
In case of a defective container module, a new set of
functional modules must be used.
In 11 Red
LED
lights
Resolution hold-open system
The hold-open system was triggered.
The hold-open system can be triggered automatically
by the smoke detector and manually by a hand trigger
button or by disengaging the door panel. According to
DIN 18263-4, the recommissioning must be deliberately
performed.
Depending on the configuration of the system, this is
done by manually opening the door up to the taught
opening angle, via the PGS by switching into the OFF
position or by a reset via the pushbuttons
and on the internal user field. It has to be ensured that
the smoke detector has not been triggered. If a reset
has not been successful, there may be a defect on the
smoke detector connection and the system must be
inspected by qualified personnel.
In 14 none The 24V for external components
is not available.
The most common cause is a short circuit of the
24V supply.
In 23 none Locking alarm
The door is blocked in the CLOSED position.
An opening is not possible.
The most frequent cause is a closed door.
The error can be avoided if a door lock switch is
installed. The door lock switch detects the switching
state of the deadbolt and switches the drive unit off,
if necessary. A door lock switch is recommended as
the permanent opening against the closed door may
damage the drive unit or the door.
In 61 none Communication error in case of a
2-panel operation
The communciation between
the 2 devices is interrupted.
The communication cable between the 2 drive units
must be checked. After a visual inspection, check if the
correct interface on the control unit has been used.
In 71 none Error in 2nd switch-off path.
2nd switch-off path test failed
After an error has been detected in the 2nd switch-
off path, the test is repeated during the next closing
movement. If there is no error then, the information is
deleted, otherwise the error is still displayed.
In 72 none Current measurement circuit
The periodically performed test of the internal
current measurement circuit could not be
successfully performed.
System tolerances and environmental conditions
influence the current measurement. That is why it
cannot always be successfully completed the first time.
The information is shown in this case This, for example,
is the case if the door is manually passed through
during the measurement. The test will be automatically
repeated.
44
dormakaba Error messages
ED 100, ED 250
Mounting instructions
WN 059799 45532
2019-07