AMS operator screens and help texts
51
Figure 24 Configuration Properties of AMS Tag (Gas table)
1 Up to four Gas Tables can be factory-installed in the
Dräger Polytron Pulsar 2 Receiver. One of those can be
selected to best suit the application. Unsuitable selection may
lead to incorrect readings and alarm levels.
2 Standard of LEL values being used to calculate table
IEC: IEC 60079-20
EN50054: EN50054
NIOSH: NIOSH ICSC
not spec.: This table is empty.
unknown: Calibration standard unknown in this version of
the device description. Contact the supplier for an upgraded
version.
3 This of the four Gas Tables is being used to calibrate and line-
arise the gas reading.
2
3
1
03023892.eps