Section 4: Configuration
3. Press the [#] and reapeat step 2 for next keypad. When finished programming all keypads, press the [#] key twice to exit
programming.
Users are assigned partition access rights via the [*][5] menu.
4.6.1 Loaned Partition Setup
To loan a keypad to another partition:
1. Press and hold [#] then key in a valid access code. The keypad switches to Global display.
2. Use the arrow keys to scroll through available partitions. Press [*] to select. The keypad is temporarily loaned to another
partition.
If the keypad is inactive for more than 30 seconds, it reverts to its assigned partition.
4.6.2 Global Zones
If a zone is added to more than one partition, it becomes a global zone. A global zone is only armed when all assigned par-
titions are armed and is disarmed when any assigned partition is disarmed.
Global zones behave as follows:
l A global Stay/Away type zone is not activated until all partitions the zone is assigned to are armed in the Away mode.
Interiors must be activated on all partitions for the global Stay/Away zone to be active.
l A shared zone bypassed on one partition is bypassed on all partitions the zone is assigned to.
l An entry delay started on a global zone sounds an entry delay on all keypads assigned to partitions the global zone
is assigned to.
l A global Delay type zone follows the longest programmed delay time of the partitions it is assigned to.
4.6.3 Fire and CO Zone Types
Fire zones only place the partition they are assigned to into alarm. Other partitions retain their current state.
A fire reset only resets partitions they are assigned to.
One or more fire zones may be located on any partition.
On alarm, the fire auto-scroll display appears on all partition keypads and on all global keypads. Fire alarm silence and fire
system reset may be done directly on any partition keypad. To silence a fire or CO alarm from a global keypad requires that
the global keypad be loaned to one of the partitions the zone is assigned to.
4.6.4 Bell/PGM Support
PGMs must be assigned to one or more partitions. See section [007] for partition assignment.
Note: Bell PGM type requires supervision and follows arming squawks by partition.
4.6.5 Communications
Account codes are assigned to all system and partition events.
For SIA communications, a single account code (programmed in section [310][000]) is used for all events. The partition is
identified via Nri1-8. System events use Nri0.
When using communication formats other than SIA, individual account codes can be programmed for each partition. See "
[310] Account Codes" on page 120.