Section 4: Configuration
4.6.6 Assign Zones
Partition zone assignments are completed using sections [201] - [208] for partitions 1 - 8. Subsections [001 - 016] are then
used to enable or disable banks of 8 zones on the partition.
4.6.7 Assign Users
Acess [*][5] using the master code, select the desired user code and enter digit 4 to modify the partitions that can accept the
user code.
4.6.8 Factory Defaults
Individual modules, as well as the alarm panel itself, can have their programming returned to factory default settings. Hard-
ware is defaulted via the following Installer Programming sections:
l [991] Default Keypads
l 000 Default all keypad programming
l 001-016 Default keypads 1-8
l [993] Default alternate communicator
l [996] Default wireless receiver
l [998] Default HSM2955
l [999] Default system
See "Defaults" on page 137 for more information.
Default All labels
Use programming section [000][999]. The following labels are returned to factory default settings:
l Zone Label
l Partition Labels
l Module Labels
l Partition 1-8 Command Output 1 to 4 Labels
l Schedule 1 to 4 Labels
l Event Labels
l User Labels
System and module programming is not affected.
Hardware Reset Main Control Panel
Perform the following to restore the main control panel to default settings:
1. Power down the system.
2. Remove all wires between Zone 1 and PGM 1 on the alarm controller.
3. Connect a short between Zone 1 and PGM.
4. Power up the system (AC only) for 60 seconds.
5. Power down the system and remove the short.
6. Power up the system again. Factory defaults are restored.
Hardware default is logged to the event buffer.
Note: Hardware default is not available when installers lockout is enabled.