PowerSeries - PC1616/PC1832/PC1864
4
1.5 AUX Power Wiring
The control panel can provide a maximum of 500mA of current for modules, powered detectors, relays, LED’s etc. If the total current required
exceeds 500mA an additional power supply is required (e.g.,PC5200, PC5204). See list below.
NOTE: AUX Output voltage: 12VDC, -15%/+15% when Input Voltage is between 85%-110% of rated value and output current between 0.0A
- 0.5A max. Refer to the list of Compatible Devices for the current draw of individual devices.
1.6 PGM Wiring
PGMs switch to ground when activated by control panel. Connect the posi-
tive side of the device to be activated to the AUX+ Terminal. Connect the
negative terminal to the PGM. Current output is as follows:
• PGM 1, 3, 4 . . . . . . . . . . . . . . . 50mA
• PGM 2 . . . . . . . . . . . . . . . . . . 300mA
For currents levels greater than 300mA a relay is required.
PGM2 can also be used for 2-wire smoke detectors.
NOTE: Use SEOL resistors on Fire Zones ONLY.
PGM 1, LED output with current limiting resistor and Optional
Relay driver output.
2-wire Smoke Detectors Initiating Circuit
Style B (Class B), Supervised, Power Limited
DC Output Voltage . . . . . . . . . . . . . . . . . . . 9.8-13.8 VDC
Detector Load . . . . . . . . . . . . . . . . . . . . . . .2mA (MAX)
Single-end-of-line (SEOL) Resistor . . . . . . . . . . . .2200
Loop Resistance . . . . . . . . . . . . . . . . . . . . . . 24(MAX)
Standby Impedance. . . . . . . . . . . . . . . . . . 1020
Alarm Impedance . . . . . . . . . . . . . . . . . . . . 570(MAX)
Alarm Current. . . . . . . . . . . . . . . . . . . . . . .89mA (MAX)
2-wire Smoke Detectors 4-wire Smoke Detectors
1.7 Carbon Monoxide Detector Wiring
RM-1/RM-2 POWER LOOP
SUPERVISORY RELAY
DSC FSA-210C Series
FSA-210C
FSA-210CT
FSA-210CS
FSA-210CST
FSA-210CLST
FSA-210CR
FSA-210CRT
FSA-210CRS
FSA-210CRST
FSA-210CLRST
FSA-410C
FSA-410CT
FSA-410CS
FSA-410CST
FSA-410CLST
FSA-410CR
FSA-410CRT
FSA-410CRS
FSA-410CRST
FSA-410CLRST
DSC FSA-410C Series
CO DETECTOR
RM-1/RM-2
POWER LOOP
SUPERVISORY
RELAY
(12V
DC
, 35mA)
ALARM
INITIATING
LOOP
RESISTANCE
100 ohm
SEOL
RESISTOR
(5600 ohm)
PC1616/1832/1864
ANY
COM
ZONE
INPUT
POWER ALARM TROUBLE
NC C NO NC C NO
ANY
Z
(SEOL TYPE 41)
AUX
+
+
-
-
+
-
DG009477
PC1616/1832/1864 v4.7 control panels support operation of
4-wire CO detectors and DSC wireless CO detectors.
Use only hardwired detectors that are compatible with the AUX
output voltage range of the DSC control panels.
NOTE: Do not loop the wire under terminals for system super-
vision. Break the wire run to provide supervision of connections.
The power supervision relay has to be powered from the last
detector in the loop.
When installing wireless CO detectors, use only DSC models
WS4913 and WS8913. DSC wireless receivers models
RF5132-433 version 5.1 (and higher), wireless transceiver
model TR5164-433 v1.0 (and higher) or RFK keypad receivers
v1.2 (and higher) are required for wireless models.