25 -3 ART Argentina Time
29 -2 BEST Brazil Eastern Standard Time
2D -1 CVT Cape Verde Time
31 0 GMT Greenwich Mean Time (UTC)
35 1 CET Central European Time
39 2 SAST South Africa Standard Time
3D 3 AST Arabic Standard Time
3F 3.5 IRST Iran Standard Time
41 4 GST Gulf Standard Time
43 4.5 AFT Afghanistan Time
45 5 PKT Pakistan Time
47 5.5 IST Indian Standard Time
48 5.75 NPT Nepal Time
49 6 VOST Vostok Time
4B 6.5 MMT Myanmar Time
4D 7 BDT Bangladesh Standard Time
51 8 CST China Standard Time
52 8.25 APO Apo Island Time
54 8.75 ACWST Australian Central Western Standard Time
55 9 KST Korea Standard Time
57 9.5 ACST Australian Central Standard Time
59 10 AEST Australian Eastern Standard Time
5B 10.5 LHST Lord Howe Standard Time
5D 11 VUT Vanuatu Time
5F 11.5 NFT Norfolk Island Time
61 12 NZST New Zealand Standard Time
64 12.75 CHAST Chatham Island Standard Time
65 13 TOT Tonga Time
69 14 LINT Line Island Time
70-FF N/A N/A N/A
[021] Account Code
Default (FFFFFF)
The account code is included when transmitting any events generated by the communicator. (e.g., panel absent trouble). It is
recommended that the account code be the same as the control panel account number. Valid range: 000001-FFFFFE. If4 digit
account codes are needed the 2 lowest digits must be programmed as FF (e.g., Account 1234 is programmed as:1234FF).
NOTE: Programming this section with all 0 or F will cause a module configuration trouble.
NOTE: This section shall sync with panel option [310] with PowerSeries Neo Panels version 1.00 or higher.
[022] Communications Format
Default (04)
Program 03 for Contact ID (CID). Program 04 for SIA. The module can be configured to send Events in SIA or CID format. The
SIA communication format follows the level 2 specifications of the SIA Digital Communication Standard - October 1997. This
format will send the account code along with its data transmission. The transmission will look similar to the following at the
receiver.
NOTE: This section shall sync with PowerSeries Neo panels version 1.00 or higher.
Example:
Nri0 ET001 where: N = New Event;ri0 = Partition/Area identifier; ET = Panel Absent Trouble; 001 = Zone 001.
14