Communications Reporting Codes
Table 8: Communications Reporting Codes
Event
SIA
Identifier
SIA
ReportingCode
CID
Qualifier
CID
Event
Code
CID
Reporting
Code
CID
User/Zone
[023] Panel Absent Trouble ET 0001 1 3 55 001
[024] Panel Absent Trouble Restore ER 0001 3 3 55 001
[026] Ethernet 1 Test Transmission RP 0001 1 6 A3 951
[027] Ethernet 2 Test Transmission RP 0002 1 6 A3 952
[030] FTC Restore YK 0001 3 3 54 001
[023] Panel Absent Trouble
Default (FF)
Program 00 to disable this event or FF to enable. This event will occur when communications with the panel have been lost for
more than 60 seconds.
[024] Panel Absent Trouble Restore
Default (FF)
Program 00 to disable this event or FF to enable. This event will occur when communications with the control panel have
resumed.
System Test Options
Test Transmissions to Primary Receiver, with Backup to Secondary Receiver:
Set Ethernet section [026] to (FF); [027] to (00).
l If the test transmission fails to the primary receiver it will backup to the secondary receiver.
l If the test transmission fails to the secondary receiver an FTC trouble will be generated.
Independent Test Transmission to Primary and Secondary Receivers:
Set Ethernet section [026] to (FF); [027] to (FF).
l The module will send periodic test transmissions to each receiver independently, with no backups.
l If the test transmission fails to any of the programmed receivers,an FTC trouble will be generated.
Alternating Test Transmission:
Alternate test transmission can be enabled or disabled in section [005] toggle option [7].
Alternating Test Transmission with backup receivers:
Set Ethernet section [026] to (FF); [027] to (00).
Interval 1:
l If the test transmission fails to the primary receiver it will backup to the secondary receiver.
l If the test transmission fails to the secondary receiver an FTC trouble will be generated.
Interval 2:
l If the test transmission fails to the secondary receiver it will backup to the primary receiver.
l If the test transmission fails to the primary receiver an FTC trouble will be generated.
Test Transmission Unique to Primary and Secondary Receivers:
Set Ethernet section [026] to (FF); [027] to (FF).
Interval 1:
l The module will send periodic test transmissions to primary receivers (Ethernet primary) independently, with no backups.
l If the test transmission fails to any of the programmed primary receivers, an FTC trouble will be generated.
Interval 2:
l The module will send periodic test transmissions to secondary receivers (Ethernet secondary) independently, with no
backups.
l If the test transmission fails to any of the programmed secondary receivers, an FTC trouble will be generated.
[026] Ethernet 1 Transmission
Default (FF)
Program 00 to disable this event transmission or FF to enable. See system test options (above) for details on settings.
[027] Ethernet 2 Transmission
Default (00)
Program 00 to disable this event transmission or FF to enable. See system test options (above) for details on settings.