Front Panel Configuration
106
9.2 ADJUSTABLE PARAMETERS
Front Panel Configuration Editor. For descriptions of the parameters, you are referred to The DSE
series Configuration Suite Manual, DSE Part 057-160.
Section Parameter As Shown On Display Values
Display
Contrast 53%
Language
English, others.
Current Date and Time
hh:mm
Timers
LCD Page Timer
5m
Scroll Delay
2s
Engine Pre Heat Timer
0s
Engine Crank Duration
10s
Engine Crank Rest Time
10s
Engine Safety On Delay
10s
Engine Smoke Limiting
0s
Engine Smoke Limiting Off
0s
Engine Warm Up Time
0s
Engine Cool Down Time
1m
Engine Speed Overshoot Delay
0s
Engine Failed To Stop
30s
Battery Under Voltage Warning Delay
1m
Battery Over Voltage Warning Delay
1m
Return Delay
30s
Generator Transient Delay
0s
Mains Transient Delay
2s
Mains transfer time
0.7s
Mains
Mains Under Voltage Alarm
184v
Mains Over Voltage Alarm
277v
Mains Under Frequency Alarm 45Hz
Mains over Frequency Alarm 55Hz
Mains Transient Delay
2s
CT Primary 600A
CT Secondary 5A
Mains kW Rating 345kW
Mains kVar Rating 258kW
Generator
Under Voltage Shutdown
184v
Under Voltage Pre-Alarm
196v
Nominal Voltage 230v
Over Voltage Pre-Alarm 265v
Over Voltage Shutdown 277v
Under Frequency Shutdown 40Hz
Under Frequency Pre-Alarm 42Hz
Nominal frequency 50Hz
Over Frequency Pre-Alarm 54Hz
Over Frequency Shutdown 57Hz
Full Load Rating 500A
kW Overload Trip 100%
Delayed Over current Active
Delayed Over Current 100%
AC System 3 Phase 4 Wire
CT Primary 600A Power Cycle After Exit
CT Secondary 5A Power Cycle After Exit
Short Circuit Trip 200%
Earth CT Primary 500A
Earth Fault Trip Active
Earth Fault Trip 10%
Transient Delay 0s
Gen Reverse Power Delay 2s
Gen Reverse Power 35kW
Engine
Oil Pressure Low shutdown 1.03bar
Oil Pressure Low Pre-Alarm 1.24bar
Coolant Temp High Pre-Alarm 90ºC
Coolant Temp High Electrical Trip 92ºC (When Enabled)
Coolant Temp High Shutdown 95ºC
Start Delay Off load 5s
Start Delay on load 5s
Start Delay Telemetry 5s
Pre Heat Timer 0s
Crank Duration 10s
Crank rest Time 10s
Safety On Delay 10s
Smoke Limiting 0s
Smoke limiting off 0s
Warm Up Time 0s
Cool Down Time 1m
Speed Overshoot Delay 0s
Speed Overshoot 0%
Fail To Stop Delay 30s
Battery Under Volts Warning Active
Battery Under Volts Warning Delay 1m
Battery Under Volts Warning 10v
Battery Over Volts Warning Active
Battery Over Volts Warning Delay 1m
Battery Over Volts Warning 30v
Charge Alternator Failure Warning Active
Charge Alternator Failure Warning 6.0v
Charge Alternator Warning Delay 5s
Charge Alternator Failure Shutdown Inactive
Charge Alternator Failure Shutdown
4.0v (When
Enabled)
Charge Alternator Shutdown Delay
5s (When
Enabled)
Droop %
Active, Inactive. Electronic engines only when
droop is enabled.
Scheduler
Scheduler Active, Inactive
Schedule On Load
Active , Inactive (Only Available When Scheduler Is
Active)
Schedule Period
Weekly, Monthly (Only Available When Scheduler Is
Active)
Schedule Time & Date Selection (1-16)
Press
to begin editing then or when
selecting the different parameters in the
scheduler.