Dunkirk PVSB - Contents; Boiler Ratings and Capacities; Gas-Fired Steam Boilers

Dunkirk PVSB
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Boiler Ratings and Capacities ...................... 2
Before You Start........................................ 3
Locating the Boiler .................................... 3
Fresh Air for Combustion ............................ 4
Installation - System Piping ......................... 5
Chimney and Vent Pipe Connection .............. 8
Vent Damper Operation .............................. 9
Gas Supply Piping .................................... 10
Electrical Wiring ....................................... 11
Controls and Accessories - What They Do ..... 17/
For Your Safety - Read Before Operating ....... 18
Operating Your Boiler ................................ 20
Checking and Adjusting ............................. 21
Cleaning Your Boiler ................................... 22
Maintaining Your Boiler .............................. 23
Service Hints ........................................... 24
Repair Parts ............................................. 25
LI
PRESSURE
GAUGE
r _T /_ "SWITCH I
....... SPILL
I I I_" l
WATER
I I L.E----I----
I [ ]L_\ /
LOW WATER
I _ CUT-OFF
- - -- ± _ -- PRORE
_ SW_TCH
L
GAS
;-.....A __ L,.E
'_'m RE_URE I
oo.TROL|
TRANSFORMER ------
_GAUGE
LOW WATER
_ $8600 CUT-OFF
VALVE
_u
LEFT SIDE FRONT RIGHT SIDE
24"
DESIGN
CERTIFIED FOR
NATURAL
AND PROPANE GAS
GAS-FIRED STEAM BOILERS
BOILER MODEL NUMBER tNATURAL GAS tPROPANE GAS
INTERMITTENT STANDING NG OF AGA HEATING NET #£T I=B=R NET
IGNITION PILOT SECTIONS INPUT CAPACITY I=B=R RATING AGA HEATING I=B=R
WITH VENT DAMPER WITH VENT DAMPER *MBH *MBH RATING,MBH PJ_IATIONS0'FT. INPUT,MBH CAPACITY,MBH RATING
*MBH
PSB-3D
PSB-4D
PSB-5D
PSB-6D
PSB-7D
PSB-8D
PSB-9D
PVSB-3D
PVSB-4D
PVSB-5D
PVSB-6D
PVSB-7D
PVSB-8D
PVSB-9D
3
4
5
6
7
8
9
75 62 47 196 70 58
112 91 68 283 !05 85
!50 122 92 383 !40 114
187 153 115 479 !75 143
225 183 137 571 210 !71
262 2!4 161 671 245 200
299 245 184 767 280 229
DIMENSIONS
_T I=B=R (Inches)
_TI_
_. F_ F_E "A"
PJW_TION D_METER WIDTH
44 !83 5 11%
64 267 6 14½
86 358 6 !7¾
107 446 7 21
!28 533 7 24¼
150 625 7 27½
172 717 7 30¾
* MBH = 1,000 Btuh. Btuh = British Thermal Unit Per Hour
**Add 5V_' to height for Vent Damper.
t For altitudes above 2,000 ft. ratingsshould be reduced at the rate of 4% for each 1,O00 ft above sea level.
Heating Capacity is based on DOE {Department of Energy} test procedure
The City of New YorkMEA Number 77-91-E.
The Ratingsmarked "Net I=B=RRatings" indicate the amount
of equivalent direct cast iron radiation each boiler will take
care of under normal conditions and thermostatic control.
The Net I=B=R Steam Ratings shown are based on an
allowance of 1.333 in accordance with the factors shown
in the t=B=RCode as published by The Hydronics Institute.
Selection of boiler size should be based upon "Net I=B=R
Rating" being equal to or greater than installed radiation in
square feet. Consult manufacturer before selecting a boiler
for installations having unusual piping and picku!_\
requirements.
Specifications and dimensions are subject to change without
notice.