EasyManua.ls Logo

Dunkirk PVSB - Installation - System Piping; Recommended Near Boiler Piping Using One Supply Tapping

Dunkirk PVSB
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The near boiler piping, that is the piping around the boiler,
must be considered as part of the boiler for proper water
level control, and to produce dry steam. Correct near boiler
piping is crucial to the proper operation of the boiler and
the heating system. Followthese recommendations carefully.
1. Place boiler in selected location, as near chimney as
possible.
2. Install the pop safety valve, using the furnished 3/4"
coupling, intothe 3/4" pipe nipple on the top ofthe boiler.
Make a discharge pipe, using 3/4' pipe (not furnished}
to carry the water or steam to a nearby drain. Do not
connect the discharge pipe directly to a drain but leave
an air gap. The downstream end of the discharge pipe
must be unthreaded. No shutoff of any description shall
be placed between the pop safety valve and the boiler,
,
,
or on discharge pipes between such safety valves and
the atmosphere. Installation of the pop safety valve shall
conform to the requirements ofthe ANSltASME Boiler and
Pressure Vessel Code, Section IVThe manufacturer is not
responsible for any water damage.
This boiler is equipped with two 21/2"supply connections
and two 21/2"return connections, one each on both the
left and right sides of the boiler. Unused connections must
be plugged with the 21/2_ plugs (furnished}.
Recommended near boiler piping for gravity return
systems is shown in Figure 5. This configuration uses one
supply and one return tapping. This setup can be used
on any size boiler in this series. The supply and return
connections may be piped both into the same side (either
left or right} or one into each side of the boiler.
POP SAFETYVALVE
FLUE
PIPEFULLSIZESAME
AS BOILERTAPPING
(2 ii2")_ MIN'
2 1/2" TEE WiTH
PLUGFOR
24"
FEED
STEAMMAINS
REDUCINGELL POINTING
DOWN
6" TO 10"
MAINVENT
1 1/2" MtN.
PIPESiZE
NIPPLE
15' MIN,
28' MIN.- DIMENSIONA
I
-- HARTFORD LOOP
WET RETURN
GATEVALVE(NOTFURNISHED)
_"'--DRAiN VALVE(FURNISHED)
FOR FLUSHINGSYSTEM
I t/2" FULLPORTBALLVALVE
FOR BOTTOMSLOWDOWN
AND DRAININGBOILER
& SYSTEM(NOT FURNISHED}
DRY RETURN
MAIN
Z4OCBF

Related product manuals