Powerbox Pro series User Manual
33
4
The battery cannot be
fully charged
Charging voltage is
too low
Adjust charging voltage
within 57.1V~57.6V range
5
The power cable sparks
once power on and ALM
indicated Red light on
Power connection
short-circuit
Turn off the battery, check
the cause of the short circuit
6
The master powerbox
Pro LED1 is yellow
flashing
Communication fault
between product and
product,or between
internal modules in
powerbox Pro
Check the external
communication cable firstly,
Check the internal
communication cable
secondly
7
The led 1,2 don’t stop
changing alternately
Modules comms
address distribution is
fault
Check the external comms
cable connection firstly.
Check the slave module DIP
setting.
If you need any technical help or have any question, please contact the dealer in time.