Description of Functional Parameter
5
EC5000
Description of Functional Parameter
Set 0,1:
S1
S2
SC
Positive run(stop when “open”)
Reverse run(stop when “open”)
two wire connecting way(set: 0)
three wire connecting way(set:1)
Run instruction(run when“closed”)
Stop instruction(stop when“open”)
Positive (reverse) rotation option
(positive when “open”;
reverse when “closed”)
Stop sw
(b contact)
Run sw
(a contact)
S2
S3
SC
S1
Set 5,6:
1.LOCAL/REMOTE selection(set 5)
To select operation by control panel or control circuit terminal.
LOCAL/REMOTE is available when AC drive stops.
OFF:run according to operation way(A03)
ON:run according to Frequency order and running order of digital
operator.
Example:set A03 to be 3.
OFF:run according to given Frequency from control circuit terminal
FV, FI and running order from control circuit terminal S1, S2.
ON: run according to Frequency order and running order from digital
operator.
2.Transmit/control circuit terminal selection (SET:6)
Select running order from transmit or control circuit terminal. This
selection function is valid only when AC drive stops.
OFF:run according to running way selection(A03)
ON:run according to the transmitted Frequency order and running
order
Set 9,10,11:
Frequency set by external joint input terminal and multi-Frequency
pre-set by A27~A29.Select 3 input terminal and their function data set to
be 9~11,then multi-frequency can be selected by ON/OFF combination. It
can offer 8 target value easily through external terminal in OFF multi-
garge value control.
Combination ON/OFF switch of terminal function S5、 S6 and S7 can
select 1-7 multistage frequency and JOG frequency. The undefined terminal
of function terminal S5、S6 and S7 act as OFF.
Notice!
OFF OFF
OFF OFF ON
OFF ON OFF
OFF ON ON
ON OFF OFF
ON OFF ON
ON ON OFF
ON ON ON
Combined joint input signal
Fre selection
11(S7) 10(S6) 9(S5)
OFF
A27 main Fre.
A28 pace 2 Fre.
A29 pace 3 Fre.
A30 pace 4 Fre.
A31 pace 5 Fre.
A32 pace 6 Fre.
A33 pace 7 Fre.
A34 JOG Fre.
Notice!
Set 13,14:select time of accelerating and reducing speed
Select pre-set time for accelerating and reducing speed from outside
terminal inputed signal. Appointed 2 input terminals to be function data
13,14,and use to accelerate and reduce speed by ON/OFF key.
Combination ON/OFF switch of terminal function RT1 and RT2 can select
1-4 acclerate and reduce speed. The undefined terminal of function terminal
RT1 and RT2 act as OFF.