SPECIFICATIONS
Eaton 5125 Tower UPS (1000–2200 VA) User's Guide S 05147304 Rev C www.eaton.com/powerquality
50
Table 4. Power Connections
Input Connection Output Receptacles
PW5125 1000 6-ft, 5-15P power cord (6) 5-15R
PW5125 1500 6-ft, 5-15P power cord (6) 5-15R
PW5125 2200 6-ft, 5-20P power cord (6) 5-15R (2) 5-20R
PW5125 2200b 15A, IEC-320 input connector (9) 10A, IEC 320-C13
PW5125 1000i 10A, IEC-320 input connector (6) 10A, IEC 320-C13
PW5125 1500i 10A, IEC-320 input connector (6) 10A, IEC 320-C13
PW5125 2200i 10A, IEC-320 input connector (9) 10A, IEC 320-C13
PW5125 1000j 6-ft, 5-15P power cord (6) 5-15R
PW5125 1500j 6-ft, 5-20P power cord (6) 5-15R
PW5125 2200j 6-ft, L5-30P power cord (6) 5-15R (2) 5-20R
Table 5. Technical Specifications
Operating Frequency 50/60 Hz, auto-sensing
Frequency Range 46–65 Hz
Noise Filtering MOVs and line filter for normal and common mode noise
Regulation
(Normal Mode)
-10% to +6% of nominal voltage
Regulation
(Battery Mode)
Nominal output voltage ±5%
Voltage Waveform Sine wave