16
Green/Red LED alter-
nave ashes every 
0.5 second and audio 
alarm beeps every 1.5 
second.
The connected loads are 
exceed the UPS capacity or 
Baery fault
The connected loads are exceed 
the UPS capacity, remove some 
noncrical loads or check if some 
loads are failed.
Red LED is on and the 
audio alarm beeps 
connuous.
A fan fault has occurred on 
the UPS. The UPS outlets are 
no longer supplied.
Check if the fan is stopped, if 
no, please contact your service 
representave.
Red LED is on and the 
audio alarm beeps 
connuous.
An internal fault has occurred 
on the UPS. The UPS outlets 
are no longer supplied.
Contact your service represen-
tave.
USB communicaon 
fails.
Cable connecon may be 
defecve.
Re-connect the USB cable, if sll 
not available. Contact your service 
representave.
7.1 Service and support
Ifyouhaveanyquesonorproblemwith the UPS, call Eatonor yourlocalser-
vicerepresentaveinyourcountry/region.Pleasehavethefollowinginformaon
readywhenyoucallforservice:
•  Model number
•  Serial number
•  Firmware version number
•  Date of failure or problem
•  Symptoms of failure or problem
•  Customerreturnaddressandcontactinformaon
Ifrepairisrequired,youwill begivenaReturnedMaterialAuthorizaon(RMA)
number. This number must appear on the outside of the package and on the Bill 
OfLading(ifapplicable).Usetheoriginalpackagingorrequestpackagingfromthe
Help Desk or distributor. Units damaged in shipment as a result of improper pack-
aging are not covered under warranty. A replacement or repair unit will be shipped 
freightprepaidforallwarranedunits.
Forcricalapplicaons,immediatereplacementmaybeavailable.Callthe
 Help Desk for the dealer or distributor nearest you.