COMMUNICATION
Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide S 164201642 Rev C www.eaton.com/powerquality
67
Table 7. IRC Wire Terminations
IRC Terminal Function Remarks
J2-1 NC
Normal mode
J2-2 COM
J2-3 NO
J2-4 NC
Bypass mode
J2-5 COM
J2-6 NO
J2-7 NC
Battery mode
J2-8 COM
J2-9 NO
J2-10 NC
Alarm mode
J2-11 COM
J2-12 NO
NOTE Maximum contact rating: 250 Vac, 30 Vdc @ 5A; Wire range: 16–24 AWG
Power Management Software
Each Eaton 9355-F47 Unirom UPS ships with power management
software and an interface cable. To begin installing power management
software, see the instructions accompanying the Software Suite CD.
NOTE Use only the supplied communication cable to connect the UPS to your computer.
Power management software provides up-to-date graphics of UPS
power and system data and power flow. It also gives you a complete
record of critical power events, and it notifies you of important UPS or
power information. If there is a power outage and the Eaton 9355-F47
Unirom UPS battery power becomes low, power management software
can automatically shut down your computer system to protect your data
before the UPS shutdown occurs.