Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide S 164201642 Rev C www.eaton.com/powerquality
78
Table 10. User Settings (continued)
Default SettingAvailable SettingsDescription
Reset Custom Event Settings 0 through 32 Total: 0/32
Auto Output Configuration Enabled/Disabled Enabled for initial startup
Disabled after initial startup
Initial Startup
Startup and operational checks must be performed by an authorized
Eaton Customer Service Engineer, or the warranty terms as specified on
page W-105 become void. This service is offered as part of the sales
contract for the UPS. Contact service in advance (usually a two-week
notice is required) to reserve a preferred startup date.
UPS Startup
W A R N I N G
Only qualified service personnel (such as a licensed electrician) should perform the UPS
installation and initial startup. Risk of electrical shock.
Verify that UPS installation has been carried out correctly and the UPS
ground has been connected.
Unirom Setup and Operation
Setup Instructions:
1. Connect input and output cables. *See user manual for
recommended minimum cable size and quantity.
2. Connect battery string or Ultracapacitor to the UPS/PFU.
3. If no remote EPO/EMO scheme is used. Leave jumper on remote
EMO switch (TB5) terminal strip and DO NOT connect wires to 24V
EMO (TB4) terminal strip.
Additional setup for optional remote EPO/EMO scheme: