Figure 18. Battery trip wiring for 93PM G2 UPS
A UPS 5 Shunt trip coil -
B External battery breaker 6 Shunt trip coil +
C External battery breaker 7 Aux contact return
1 BAT_Shunt_DET 8 Aux contact
2 GND 9 Shunt trip coil -
3 Aux contact return 10 Shunt trip coil +
4 Aux contact
55..44 IInnssttaalllliinngg UUPPSS eexxtteerrnnaall bbaatttteerryy ccaabbiinneett aanndd bbaatttteerryy ppoowweerr ccaabblliinngg
There is a vast offering of different Eaton external battery cabinets available for the 93PM G2 UPSs.
Please refer to the three-phase accessories offering for further details. See a separate manual for
instructions on how to install Eaton external battery cabinets.
NOTE: Do not connect battery strings with different battery quantity and voltage in parallel.
EATON 93PM G2 UPS USER’S AND INSTALLATION GUIDE P-164000956
-