8 Eaton 9PX Lithium-Ion User Guide P-164001006—Rev 02
Table 4. LCD Operating Status (Continued)
Operation status Cause Description
High Efficiency mode
The UPS is operating on High Efficiency
mode.
The UPS is powering and protecting the
equipment
Bypass mode
An overload or a fault has occurred, or a
command has been received, and the
UPS is in Bypass mode.
Equipment is powered but not protected
by the UPS.
22..66 DDiissppllaayy FFuunnccttiioonnss
Press the ( ) button to activate the menu options. use the two middle buttons ( and ) to scroll through
the menu structure. Press the (
) button to select an option. Press the ESC button to cancel or return to the
previous menu.
Table 5. Display Functions
Main menu Submenu Display information or Menu function
Measurements
[Load] W VA A pf / [Input/Output] V Hz /
[Efficiency] % / [Battery] % min V n°
EBM / [Battery remaining life] months /
[Average power usage] Wh / [Cumulated
power] Wh / BMS Information
Control Go to Bypass Transfers the UPS on Bypass mode
Load segments On/Off Commands the load segments
Start battery test Starts a manual battery test
Connectivity test Tests dry contact relay outputs and relay
card contacts. Simulates line failure and
battery low
Function reset Clears active fault, power usage, battery
remaining life, reset NMC, Restore
factory settings.
Settings Local settings Sets product general parameters
In/out settings Sets Input and Output parameters
On/Off settings Sets On/Off conditions
Battery settings
Sets battery configuration
Com settings Sets communication parameters
Event Log Event filter Selects faults, alarms and/or events to
display
Event list Displays the events stored
Reset fault list Clears events
Display Functions