DeviceNet Configuration
14 C440/XTOE Electronic Overload Relay, DeviceNet MN04210002E—March 2011 www.eaton.com
DeviceNet Configuration
DeviceNet Baud Rate Configuration DIP Switches 7, 8
The DeviceNet baud rate is configured using the DIP
switches on the face of the device.
DIP Switch Baud Rate Selection
DeviceNet MAC ID Selection
The DeviceNet MAC ID is configured using the DIP switches
on the face of the device.
DIP Switch Behavior
Note: To set a MAC ID of 25, DIP switches 5, 4 and 1 need
to be turned on, with all others off. Default is Mac ID
63 (all on).
C440 DeviceNet Object Details
C440 DeviceNet Full Profile
Identity Object, Class 0x01 (C440)
Identity Instance Services (C440)
B0 (Sw7) B1 (Sw8) Baud
Off Off 125k (default)
On Off 250k
Off On 500k
On On Software configuration
DIP Switch Value
632
516
48
34
22
11
632
Class Object Number of Instances
0x01 Identity 1
0x02 Message router 1
0x03 DeviceNet 1
0x04 Assembly 7 (See assembly object details)
0x05 Connection 3
0x08 Discrete input point 4
0x09 Discrete output point 2
0x29 Control supervisor 1
0x2C Overload 1
0x94 DeviceNet interface 1
Service
Code
Service
Name
Service
Data Description
0x05 Reset 0 Instance 1: Initializes adapter to the
power-up state
0x05 Reset 1 Instance 1: Writes default values to
all instance attributes AND then
saves all non-volatile attributes to
flash memory and then performs the
equivalent of a reset (0)
0x05 Reset 101 Vendor specific reset—perform
Intercom divorce. If comm module is
not connected to a C440, the comm
module will assume the discrete IO
profile. If the comm module is
connected to a C440, it will marry to
the C440 and assume the
overload profile.
0x0E Get_Attributes
_Single
N/A Returns the contents of the
specified data
0x10 Set_Attributes
_Single
Value Modifies an attribute value
C440 DeviceNet.book Page 14 Friday, March 25, 2011 10:41 AM