DeviceNet Configuration
24 C440/XTOE Electronic Overload Relay, DeviceNet MN04210002E—March 2011 www.eaton.com
Discrete Input Object, Class 0x08 (C440)
Discrete Input Point Instance Services (C440)
Discrete Input Point Object Instance #1–4 (C440)
Input Point Value
The input point value reflects current state of the associated
input terminal.
Discrete Output Object, Class 0x09 (C440)
The Discrete Output Point (DOP) Object models discrete
outputs in a product. Note that the term “output” is defined
from the network’s point of view. An output will consume
data from the network. The output is read from this object’s
VALUE attribute and applied to the output terminal.
Discrete Output Point Instance Services (C440)
Discrete Input Point Object Instance #1–4 (C440)
Output Point Value
The output is read from this object’s VALUE attribute and
applied to the output terminal.
Communication Fault Action
Determines the action to be taken at the output terminal
when a communications fault occurs.
If this attribute is set to “0,” then output terminal will be set
to the state determined by attribute “Communications fault
value.”
If the attribute is set to “1,” then the output terminal is not
changed due to a communications fault.
Default: “0”
Communication Fault Value
Determines the value to be applied to the output terminal if a
communications fault occurs
AND the “Communication fault action” attribute is set
to “0.”
Default: 0.
Idle Action
Determines the action to be taken at the output terminal when
communication idle occurs. If this attribute is set to “0,” then
output terminal will be set to the state determined by attribute
“Idle value.”
If the attribute is set to “1,” then the output terminal is not
changed due to a communications idle event.
Default: “0”
Idle Value
Determines the value to be applied to the output terminal if
a communications idle event occurs AND the “Idle action”
attribute is set to “0”.
Default: 0.
Service
Code Service Name
Service
Data Description
0x0E Get_Attributes_Single N/A Returns the contents of the
specified data
0x10 Set_Attributes_Single Value Modifies an attribute value
Attr
ID
Access
Rule NV Name
Data
Type Attribute Description
3 Get — Value BOOL Input point value
101 Set — Debounce UDINT Debounce time
Service
Code Service Name
Service
Data Description
0x0E Get_Attributes_Single N/A Returns the contents of the
specified data
0x10 Set_Attributes_Single Value Modifies an attribute value
Attr
ID
Access
Rule NV Name
Data
Type Attribute Description
3 Set — Value BOOL Output point value (see below
for details)
5 Set NV Fault
action
BOOL Action taken on output’s value
in communication fault state
(see below for details)
6 Set NV Fault
value
BOOL User-defined value for use with
fault action attribute (see
below for details)
7 Set NV Idle
action
BOOL Action taken on output’s value
in communication idle state
(see below for details)
8 Set NV Idle
value
BOOL User-defined value for use with
idle action attribute (see below
for details)