DeviceNet Configuration
20 C440/XTOE Electronic Overload Relay, DeviceNet MN04210002E—March 2011 www.eaton.com
Input Assembly 120 and 130 Selection List (C440)
Output Assembly 2
Output Assembly 105
Output Assembly 111—Bit Strobe Command (C440)
Sixty-four bits of strobe data, one per MAC ID. The data is
ignored by the C440 DeviceNet adapter.
Connection Object, Class 0x05 (C440)
Connection Instance Services (C440)
Value Description
0 Assembly terminator
1 Device status
2 RMS current IA
3 RMS current IB
4 RMS current IC
5 RMS current average
6 Current as a percent of FLA
7 Phase imbalance percentage
8 Frequency
9 Overload thermal pile memory
percentage
10 Present fault bits (trip reason)
11 Feature status
12 Device temperature
13 Ground current (RMS)
14 Ground fault percentage
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 —————Fault
reset
——
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 — — Test
trip
— — Fault
reset
Out 2 Out 1
Service
Code
Service
Name
Service
Data Description
0x05 Reset N/A Resets the inactivity/
watchdog timer
Transitions from timed-out or
deferred delete state to
established
0x0E Get_Attributes_Single N/A Returns the contents of the
specified data
0x10 Set_Attributes_Single Value Modifies an attribute value
C440 DeviceNet.book Page 20 Friday, March 25, 2011 10:41 AM
For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616