EasyManua.ls Logo

Eaton C440/XTOE - Explicit Messaging Connection Attributes; Polled I;O Connection Attributes

Eaton C440/XTOE
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DeviceNet Configuration
22 C440/XTOE Electronic Overload Relay, DeviceNet MN04210002E—March 2011 www.eaton.com
Connection Object Instance #2 Attributes (Polled I/O) (C440)
Attr ID
Access
Rule NV Name Data Type Attribute Description
1 Get State USINT State of the object
Default = 0x01
2 Get Instance_Type USINT Indicates either I/O or messaging connection
Default = 0x01
3 Get TransportClass_Trigger BYTE Defines behavior of the connection
Default = 0x83
4 Get Produced_Connection_ID UINT Placed in CAN identifier field when the connection transmits
5 Get Consumed_Connection_ID UINT CAN Identifier field value that denotes message to be received
6 Get Initial_Comm_Characteristics BYTE Defines the message group(s) across which productions and consumptions
associated with this connection occur
Default = 0x01
7 Get Produced_Connection_Size UINT Maximum number of bytes transmitted across this connection
8 Get Consumed_Connection_Size UINT Maximum number of bytes received across this connection
9 Get/Set Expected_Packet_Rate UINT Defines timing associated with this connection
Default = 0x0000
10 _11 N/A N/A N/A Not used. These attribute IDs have been obsoleted and are no longer defined
for a connection object
12 Get/Set Watchdog_Timeout_Action USINT Defines how to handle inactivity/watchdog timeouts
Default = 0x00
13 Get Produced_Connection_Path_Length UINT Number of bytes in the Produced_Connection_Path attribute
Default and fixed as 0x03
14 Get/Set NV Produced_Connection_Path Packed
EPATH
Specifies the application object(s) whose data is to be produced by this
connection object default assembly instance 120 “0x62 0x37 0x38”
Allowed EPATHs:
50 (0x32): “0x62 0x33 0x32”
107 (0x6B): “0x62 0x36 0x42”
120 (0x78): “0x62 0x37 0x38”
130 (0x82): “0x62 0x38 0x32”
15 Get Consumed_Connection_Path_Length UINT Number of bytes in the Consumed_Connection_Path attribute
Default and fixed as 0x03
16 Get/Set NV Consumed_Connection_Path Packed
EPATH
Specifies the application object(s) that are to receive the data consumed by
this connection object
Default assembly instance 105 “0x62 0x36 0x39”
Allowed EPATHs:
2 (0x02 ): “0x62 0x30 0x32”
105 (0x69 ): “0x62 0x36 0x39”
C440 DeviceNet.book Page 22 Friday, March 25, 2011 10:41 AM
For Immediate Delivery or Tech Support call KMParts.com at (866) 595-9616

Table of Contents

Related product manuals