Technical Data and Specifications
C440/XTOE Electronic Overload Relay, DeviceNet MN04210002E—March 2011 www.eaton.com 7
Electronic Overload Relays Up to 1500A—Ratings and Specifications, continued
Short Circuit Ratings
Short Circuit Ratings (North America CSA, cUL)
Changes to UL 508A and NEC in recent years have brought a focus to control panel safety with regard to short-circuit current
ratings (SCCR). Eaton’s C440 electronic overload relays combined with XT series IEC and Freedom Series NEMA contactors
provide a wide variety of SCCR solutions needed for a variety of applications. The SCCR data in this document reflects the
latest information as of April 2010.
C440/XT Standalone Overload Relays (XT, C440)
Specification
Description 45 mm 55 mm
Electrical/EMC, continued
Surge immunity
IEC 60947-4-1 (Table 13)
IEC 61000-4-5 a Class 4
Three-phase power inputs:
±4 kV line-to-line (DM)
±4 kV line-to-ground (CM)
Three-phase power inputs:
±4 kV line-to-line (DM)
±4 kV line-to-ground (CM)
With accessory installed in expansion bay:
±2 kV line-to-line (DM) –>1.2/50 us;
2 kV line-to-earth, 1 kV line-to-line
±4 kV line-to-ground (CM)
With accessory installed in expansion bay:
±2 kV line-to-line (DM) –>1.2/50 us;
2 kV line-to-earth, 1 kV line-to-line
±4 kV line-to-ground (CM)
Power freq. magnetic field immunity
IEC 60947-4-1, IEC 61000-4-8
30A/m, 50 Hz 30A/m, 50 Hz
Electromagnetic field
IEC 60947-4-1 Table 13, IEC 61000-4-3
10V/m 10V/m
Distortion IEEE 519 5% THD max., 5th harmonic 3% max. 5% THD max., 5th harmonic 3% max.
Electrostatic discharge (ESD)
IEC 61000-4-2, EN 61131-2
4 kV contact
8 kV air discharge
4 kV contact
8 kV air discharge
Electrical fast transient (EFT)
IEC 61000-4-4, EN 61131-2
±2 kV using direct method ±2 kV using direct method
Surge immunity
IEC 61000-4-5, EN 61131-2
±2 kV line-to-ground (CM) ±2 kV line-to-ground (CM)
Overload
FLA Range
Maximum
Operating
Voltage
Standard-Fault Short Circuit Data High-Fault Short Circuit Data
600V
(kA)
Maximum
Fuse Size (A)
(RK5)
Maximum
Breaker
Size (A)
Fuses (RK5, J, CC) Thermal-Magnetic Circuit Breakers
480V
(kA)
600V
(kA)
Maximum
Fuse Size
480V
(kA)
600V
(kA)
Maximum
Breaker Size
0.33–1.65A 600 Vac 1 6 15 — — — — — —
1–5A 600 Vac 5 20 20 100 100 30 100 35 20
4–20A 600 Vac 5 80 80 100 100 100 100 35 80
9–45A 600 Vac 5 175 175 100 100 100 100 35 100/175 (480/600)
20–100A 600 Vac 10 400 400 100 100 200 150 35 250/400 (480/600)
C440 DeviceNet.book Page 7 Friday, March 25, 2011 10:41 AM