EasyManua.ls Logo

Eaton C441R - Page 43

Eaton C441R
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
43
User Manual MN04200002E
Effective January 2016
C441 Ethernet module user manual
(C441R, C441T, C441U, C441V)
EATON www.eaton.com
Table 84. Class 41 (0x29): Control Supervisor Object
Instance Count: 1
Instance List: 1
Attrib NV Access
Data
Type Name Description
3 (0x03) V Set/Get BOOL Run1 Run the softstarter.
4 (0x04) V Set/Get BOOL Run2 Run the softstarter(ramp2)
7 (0x07) V Get BOOL Running1 Indicates if the motor is run-
ning standard ramp
8 (0x08) V Get BOOL Running2 Indicates if the motor is run-
ning ramp2
9 (0x09) V Get BOOL Ready Softstarter is not faulted
10 (0x0A) V Get BOOL Faulted Fault present
11 (0x0B) V Get BOOL Warning Warning present
12 (0x0C) V Set/Get BOOL Fault Reset Reset Fault
15 (0x0F) V Get BOOL Control From
Net
Control is coming from the
network.
22 (0x16) V Get UDINT Total motor
starts
Total Motor Starts
100 (0x64) NV Set/Get USINT S811 Input1 cfg Entry 1
101 (0x65) NV Set/Get USINT S811 Input2 cfg Entry 2
102 (0x66) NV Set/Get USINT S811 Input3 cfg Entry 3
103 (0x67) NV Set/Get USINT S811 Input4 cfg Entry 4
104 (0x68) NV Set/Get USINT C441 Input1 cfg Entry 5
105 (0x69) NV Set/Get USINT C441 Input2 cfg Entry 6
106 (0x6A) NV Set/Get USINT C441 Input3 cfg Entry 7
107 (0x6B) NV Set/Get USINT C441 Input4 cfg Entry 8
108 (0x6C) NV Set/Get USINT S811 FormA
relay cfg
Entry 1
109 (0x6D) NV Set/Get USINT S811 FormC
relay cfg
Entry 2
110 (0x6E) NV Set/Get USINT C441 Output1
relay cfg
Entry 3
111 (0x6F) NV Set/Get USINT C441 Output2
relay cfg
Entry 4
112 (0x70) NV Set/Get UINT Custom fault
code 1
Entry 1
113 (0x71) NV Set/Get UINT Custom fault
code 2
Entry 2
114 (0x72) NV Set/Get UINT Custom fault
code 3
Entry 3
115 (0x73) NV Set/Get BOOL Terminal Block
control enable
Enables Local control at the
terminal block
116 (0x74) V Get BOOL Run1 logic
sense
Status of Run1 input logic
sense (edge/level)
117 (0x75) NV Set/Get BOOL wiring config 0 - standard wiring; 1 -
Inside the delta wiring
118 (0x76) NV Set/Get BOOL Pending start
warning
Enables warning when
start delay timers are used.
Warning is issued while
start command is pending
119 (0x77) NV Set/Get UINT Power up start
delay
Time delay after power up
before a start command can
be issued
120 (0x78) NV Set/Get UINT Start delay Time delay after a start com-
mand is issued before the
S811+ will attempt start
121 (0x79) NV Set/Get UINT Run cmd start
delay
User settable time delay
between successive
start profiles. Delay
becomes active when start
profile(ramp vs ramp2)
changes between starts
122 (0x7A) V Get UINT Auto Reset
Count
Number of auto reset
attempts
Table 83. Class 10 (0x0A): Analog Input Object
Instance Count: 1
Instance List: 1
Attrib NV Access
Data
Type Name Description
3 (0x03) V Get USINT Analog Input
Value (% of
range)
Analog input reading (in percent of
set range)
8 (0x08) V Get USINT Analog Value
Data Type
Analog Input Value Data Type
0 - INT
1 - REAL
2 - USINT
3 - SINT
4 - DINT
5 - LINT
6 - UINT
7 - UDINT
8 - ULINT
9 - LREAL
100 - (Vendor specific) USINT -
Value in % of selected range (only
format supported)
100
(0x64)
V Get USINT Analog Input
Status
Status of the S811+ analog input
0x00 - Not Active
0x01 - Input under range
0x02 - Input over range
0x03 - Input in overdrive
0x04 - Input is in range
101
(0x65)
NV Set/Get USINT Analog Input
Data Range
Selected range of analog input
0x02 0-20mA range
0x03 4-20mA range
102
(0x66)
NV Set/Get USINT Analog Input
Trip Enable
Analog input trip enable
0x00 - disable
0x01 - fault enable
0x02 - warning enable
103
(0x67)
NV Set/Get USINT Analog Input
Trip Low
Threshold
Low analog input trip threshold (in
percent of selected analog range)
104
(0x68)
NV Set/Get USINT Analog Input
Trip High
Threshold
High analog input trip threshold (in
percent of selected analog range)
105
(0x69)
NV Set/Get UINT Analog Input
Trip Duration
Amount of time a low or high
analog input condition must exist
before a trip; 0.0 - 60.0 (in 0.1secs)

Related product manuals