Fault 004, UPS Temp. High
Start
Room temperature
is high?
Decrease
room temperature
Y UPS temperature fault? EndN
UPS surrounding temperature
is high?
N
Y
Remove heat sourceY UPS temperature fault? N End
Confirm outtake airflow on rear
panel is block?
N
Clear dust or object
Y
Y UPS temperature fault?
EndN
Check Fan is rolling normally?
Clear dust or object
UPS temperature
fault?
EndN
Y
End
Client Environment
UPS
Check CNTL
CNTL
Replace CNTL PCBAN
UPS temperature
fault?
EndN
Check PSDR
PSDR
Y
Replace damaged
components
UPS temperature
fault?
N
Replace PSDR
Y
Y
EndN
Y
N
N
Y