EATON Diesel Plus O & M Manual IM05805019K
Diesel Engine Fire Pump Controller Effective June 2011
EATON CORPORATION www.ceaton.com 11
Following is a description of each programmable set point.
Please Enter Password - If the password is enabled, the user will
be prompted to enter the password at this time. If there are no
buttons pressed for five (5) seconds, the controller will switch
back to the automatic mode.
Language - Three (3) languages are offered as standard. They
are English, French, or Spanish. A fourth language can be
added utilizing the USB port. Consult Eaton for available
languages. Refer to for programming.
Regional Settings - Refer to Appendix B. Following are the
descriptions of each menu item:
• Change Date - Factory set, however, this parameter allows the
user to set the current date.
• Change Time - Factory set to Mountain Standard Time (MST).
This menu item allows the user to adjust the time to the local
time. The clock is of the 24-hour type.
Pressure Settings - Refer to Appendix C. Following are the
descriptions of each menu item:
• Pressure Sensor - Some applications do not require a
pressure sensor to sense the system pressure in order to
start the pump motor when required. The pressure sensor
can be disabled through this menu item, in order to
accomplish this. Once disabled, the pressure start point,
pressure stop point, low pressure alarm, and high pressure
alarm set-points will be removed from the menu system.
• Pressure Start Point - The value programmed determines at
which pressure the controller will initiate a start sequence.
• Pressure Stop Point - The value programmed determines the
pressure the system must reach before the controller will
automatically stop the fire pump motor, via the running
period timer. If the system pressure does not exceed the
programmed Pressure Stop Point, the fire pump motor will
continue to run. (Auto Shutdown must be set to ON)
Ta b l e 1. Programmable Features and Set Points
Description Factory Default Range
Main Program - Appendix A
Language - Appendix A
Regional Settings - Appendix B
English English/French/Spanish
Change Date Current Date Unlimited
Change Time Current Time (MST) 24 Hours
Pressure Settings - Appendix C
Pressure Sensor Enabled Enabled/Disabled
Pressure Start Point 100 PSI 0-500 PSI
Pressure Stop Point 110 PSI 0-500 PSI
Low Pressure Alarm Point 105 PSI 0-500 PSI
High Pressure Alarm Point 300 PSI 0-500 PSI
Auto Shutdown OFF ON/OFF
Proof Pressure Switch Disabled Enabled/Disabled (Foam Only)
Low Suction Shutdown (Foam Level) Disabled Disabled/Enabled
Pressure Deviation 10 PSI 1-50 PSI
Hourly Pressure Recording Disabled Enabled/Disabled
Timer Values - Appendix D
Run Period Timer 10 Minutes 0-45 Minutes
RPT Start Mode Pump Run Pump Run/Pressure Stop Point
Weekly Test Timer Disabled 7 Days/24 Hours (1-60 Minutes)
AC Power Failure Alarm 5 Seconds 0-180 Seconds
AC Power Failure Start Disabled Disabled/Enabled
Sequential Start Timer Disabled Disabled / 1-300 Seconds
Custom Input/Output - Appendix E
Custom Inputs #1-10 Undefined Refer to Appendix E(a)
Custom Outputs #1-10 Undefined Refer to Appendix E(b)
Custom Lights #1-6 Undefined Refer to Appendix E(c)
Main Menu Password - Appendix F Disabled Enabled/Disabled - Any number of four (4) button combinations from keypad