O & M Manual IM05805019K EATON Diesel Plus
Effective June 2011 Diesel Engine Fire Pump Controller
30 EATON CORPORATION www.eaton.com
9.4 Weekly Exerciser Test
Turn the mode selector switch to the “OFF” position.
To test the Weekly Exerciser, preprogram the controller to
initiate the test at a time suitable to the user.
Turn the mode selector switch to the “AUTO” position.
At the programmed time and date the drain valve solenoid will
open. The Engine will crank and start. The “Engine Run
annunciator will illuminate.and the drain valve solenoid will
close.
Press the STOP pushbutton.
The engine will stop.
Reprogram Weekly Exerciser for normal operation.