EasyManua.ls Logo

Eaton Digitrip 520 - List of Figures

Eaton Digitrip 520
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3
Instructional Leaflet IL70C1037H05
Effective October 2009
Digitrip models 520, 520i; and 520M, 520Mi,
520MC, 520MCi trip units for use only in
Magnum and Magnum DS circuit breakers
EATON CORPORATION www.eaton.com
Figure 1. Digitrip 520MC Trip Unit with Rating Plug . . . . . . . . . . . . 5
Figure 2. Installation of the Digitrip Unit into a Magnum Breaker
(Side View). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 3. Installation of the Rating Plug and Mounting Screw . . . . 9
Figure 4. Ground Alarm/Power Supply Module for the
520M or 520MC Trip Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 5. Wiring Diagram for 520M and 520MC Models
with Ground Alarm/Power Supply Module . . . . . . . . . . . . . . . . . . 10
Figure 6. Tripping Circuit for a Typical Magnum
Breaker (Partial) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 7. Three-Pole, Four-Wire Breaker with
Neutral Sensor Connections for 3200A Frame
Using Residual Ground Fault Sensing . . . . . . . . . . . . . . . . . . . . . . 13
Figure 8. Neutral Sensor Connections for 4000A Frame
Using Residual Ground Fault Sensing . . . . . . . . . . . . . . . . . . . . . . 13
Figure 9. Digitrip Neutral Sensor Types (or Source Ground Sensor) 14
Figure 10. Four-Pole 3200A Frame (4000A IEC) Using Residual
Ground Fault (Earth-Fault) Sensing . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 11. Source Ground Fault Sensing Scheme
for 3200A Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Figure 12. Source Ground Fault Sensing Scheme
for 4000A Frame—Double-Wide . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 13. Zero Sequence Sensing Scheme for 3200A Frame . . . 16
Figure 14. Multiple Source/Multiple Ground Scheme . . . . . . . . . . 16
Figure 15. Block Diagram with Breaker Interface . . . . . . . . . . . . . 18
Figure 16. Digitrip 520 LI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 17. Digitrip 520 LSI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 18. Digitrip 520 LSIG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 19. Digitrip 520i WLSIG . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Figure 20. Digitrip 520M MLSI . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 21. Digitrip 520M MLSIA . . . . . . . . . . . . . . . . . . . . . . . . . .20
Figure 22. Digitrip 520M MLSIG . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 23. Digitrip 520Mi MWLSIG . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 24. Digitrip 520MC CLSI . . . . . . . . . . . . . . . . . . . . . . . . . . 21
List of figures
Description Page Description Page
Figure 25. Digitrip 520MC CWLSIG . . . . . . . . . . . . . . . . . . . . . . .21
Figure 26. Digitrip 520MC ARMLSI . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 27. Digitrip 520MC ARMLSIG . . . . . . . . . . . . . . . . . . . . . . 21
Figure 28. Digitrip 520MC ARMLSIA . . . . . . . . . . . . . . . . . . . . . .22
Figure 29. Digitrip 520MC ARMWLSIG . . . . . . . . . . . . . . . . . . . .22
Figure 30. Long Delay Current Settings . . . . . . . . . . . . . . . . . . . . 22
Figure 31. Long Delay Time Settings . . . . . . . . . . . . . . . . . . . . . . 23
Figure 32. Long Time Memory (LTM) Jumper . . . . . . . . . . . . . . . 23
Figure 33. Short Delay Current Settings . . . . . . . . . . . . . . . . . . . . 23
Figure 34. Short Delay Time Settings . . . . . . . . . . . . . . . . . . . . . . 24
Figure 35. Instantaneous Current Settings . . . . . . . . . . . . . . . . . .24
Figure 36. Ground Fault Current Settings . . . . . . . . . . . . . . . . . . . 24
Figure 37. Ground Fault Time Delay Settings . . . . . . . . . . . . . . . .25
Figure 38. INCOM Network with Remote Master
Computer or BIM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Figure 39. Functional Test Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 40. Connection Details for Conducting Single-Pole,
Single-Phase Current Tests with the Breaker Removed
from the Cell . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 41. Connection Details for Conducting Single-Phase
Current Tests with the Breaker Removed from the Cell. . . . . . . . 28
Figure 42. Alternate Connection Details Using Three Poles
to Develop a Ground Fault Condition . . . . . . . . . . . . . . . . . . . . . . 28
Figure 43. Digitrip Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Figure 44. Typical Trip Function Record Nameplate . . . . . . . . . . . 30
Figure 45. Automatic Trip Operation Record . . . . . . . . . . . . . . . . . 30
Figure 46. Typical Performance Test Record Form . . . . . . . . . . . . 31
Figure 47. Maintenance Mode Wiring—Digitrip 520MC . . . . . . . . 33
Figure 48. Typical Zone Interlocking . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 49. Typical Zone Interlocking Connections with
Two Main Breakers (M1, M2) and a Tie Breaker (T) . . . . . . . . . . . 35
Figure 50. Typical Breaker Master Connection Diagram . . . . . . . . 37
Figure 51. Modbus Translator Wiring . . . . . . . . . . . . . . . . . . . . . . 38

Table of Contents

Related product manuals