50P[2].Mode
Non-directional
Forward
E_FAF
1.
2.
Press “▼” (Down) repeatedly again, until the
required value, for instance: “Non-directional”,
is highlighted.
Then press the »Ok« key, so that this
new value gets stored (temporarily). (Or,
alternatively, press the »Ack/Rst« key to cancel
the modi󰊟cation.)
Note that the new value is only stored
internally, but not active yet.
Operational
Info
Ack/Rst
Ok
CTRL
E_FAG
Device Planning
ℹ General Operation Mode
50P[2].Mode
Non-directional
That 󰊟rst »Ok« pressing that you have just
done brings you back to the screen showing the
selected parameter, »50P[2] . Mode«.
However, some things have changed now:
Now the new value “Non-directional” is
shown.
An asterisk character “*” next to the
parameter indicates that there are
temporary changes for it. In addition,
another asterisk next to the heading line
indicates that parameter changes exist
that have not yet been accepted and
activated by the device. (The “*” remains
there, even if one navigates to some
other menu branch. See also ╚═▷ “Asterisk
(Star)”.)
In the top right corner of the display,
an open lock symbol indicates that the
entered password is still e󰊞ective, i. e. the
respective access level is open.
Operational
Info
Ack/Rst
Ok
CTRL
E_FAH
Save Parameter changes?
Save
YesNo
?
Press »Ok« again. (In principle, this can also
be done later, i. e. after some more parameter
changes and when being in another menu
branch.)
A con󰊟rmation dialog asks you to explicitly
accept your changes. Press the corresponding
Softkey for “Yes” (or “No” to cancel).
The protection device performs a validity
check, and after this, it uses the new setting
(unless it detects a validity problem).
If the validity check should fail, i. e. the protection device detects some validity problem
or incosistency with respect to the new value(s) then this is indicated by a big “?
character that appears instead of the “*” in the heading line. In this case the protection
device refuses to activate the new value(s), and you are expected to re-edit the values.
40 www.eaton.com E-Series Family Quick Start Guide
3 Quick Start – Operation via Panel
3.7 Parameter Changes – “Ok” key