5.2.4
Relay Outputs (Binary Outputs)
Enter the menu [Device Para / Relay Outputs] and all sub-menu items therein (depending
on your hardware, i. e. which slots are 󰊟tted with Relay Outputs), for example [Device Para /
Relay Outputs / RO Slot X2 / RO 1].
Set the parameters for the operating mode, hold and delay times, latching, the
reset (acknowledgment) signal (if »Latched« is set to “Active”), and for up to
7 binary output signals, you can assign a digital output signal to the Relay Output
(parameters »Assignment 1«, …, »Assignment 7«) and decide about »Inverting x« for
this signal.
This de󰊟nes which signals shall be indicated by Relay Outputs. If any of the 7 assigned
signals becomes true, the Relay Output becomes either active (if »Inverting« = “Inactive”),
or vice versa (if »Inverting« = “Active”).
5.2.5 LED Assignment
Enter the menu [Device Para / LEDs].
Set the parameters for latching, the acknowledgment signal (if »Latched« is set to Active”),
the active and inactive LED color and 󰊠ashing mode, and for up to 5 binary output signals,
you can assign the signal to the LED (parameters »Assignment , …, »Assignment ) and
decide about »Inverting x« for this signal.
This de󰊟nes which signals shall be made visible by LEDs. If any of the 5 assigned signals
becomes true, the LED is lit in the active color, otherwise it is lit in the inactive color. (Both
colors may also be set to “-”, which means the LED is o󰊞.)
5.2.6
System Settings
Enter the menu [System Para], including all available sub-menus, and set all
parameters that de󰊟ne the “surrounding” settings (i. e. the “system connected to the
protection device”).
In particular, take care of the following settings:
[System Para / General Settings] »Phase Sequence« selects the phase sequence
(“ABC” or “ACB”).
[System Para / General Settings] »f« selects the nominal frequency (“50” or “60”).
[System Para / VT] »Main VT con« selects the type of phase voltages (“Open-Delta”,
i. e. delta connection, or “Wye”, i. e. star connection).
[System Para / VT] »Main VT pri« sets the nominal primary voltage Vn. Note that this
is always the phase-to-phase voltage (independent of the connection type).
[System Para / VT] »Main VT sec« sets the nominal secondary voltage Vn. Note that
this is always the phase-to-phase voltage V LL (independent of the connection type).
76 www.eaton.com E-Series Family Quick Start Guide
5 Con󰊟guration via PowerPort-E
5.2.4 Relay Outputs (Binary Outputs)

Other manuals for Eaton E Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton E Series and is the answer not in the manual?

Eaton E Series Specifications

General IconGeneral
SeriesE Series
Operate Time15 ms
Contact ArrangementDPDT
Electrical Life100, 000 operations
Vibration Resistance10-55 Hz, 1.5 mm
Mechanical Life10, 000, 000 operations

Related product manuals