5.2.4
Relay Outputs (Binary Outputs)
Enter the menu [Device Para / Relay Outputs] and all sub-menu items therein (depending
on your hardware, i. e. which slots are tted with Relay Outputs), for example [Device Para /
Relay Outputs / RO Slot X2 / RO 1].
Set the parameters for the operating mode, hold and delay times, latching, the
reset (acknowledgment) signal (if »Latched« is set to “Active”), and for up to
7 binary output signals, you can assign a digital output signal to the Relay Output
(parameters »Assignment 1«, …, »Assignment 7«) and decide about »Inverting x« for
this signal.
This denes which signals shall be indicated by Relay Outputs. If any of the 7 assigned
signals becomes true, the Relay Output becomes either active (if »Inverting« = “Inactive”),
or vice versa (if »Inverting« = “Active”).
5.2.5 LED Assignment
Enter the menu [Device Para / LEDs].
Set the parameters for latching, the acknowledgment signal (if »Latched« is set to “Active”),
the active and inactive LED color and ashing mode, and for up to 5 binary output signals,
you can assign the signal to the LED (parameters »Assignment 1«, …, »Assignment 5«) and
decide about »Inverting x« for this signal.
This denes which signals shall be made visible by LEDs. If any of the 5 assigned signals
becomes true, the LED is lit in the active color, otherwise it is lit in the inactive color. (Both
colors may also be set to “-”, which means the LED is o.)
5.2.6
System Settings
Enter the menu [System Para], including all available sub-menus, and set all
parameters that dene the “surrounding” settings (i. e. the “system connected to the
protection device”).
In particular, take care of the following settings:
• [System Para / General Settings] »Phase Sequence« selects the phase sequence•
(“ABC” or “ACB”).
• [System Para / General Settings] »f« selects the nominal frequency (“50” or “60”).•
• [System Para / VT] »Main VT con« selects the type of phase voltages (“Open-Delta”,•
i. e. delta connection, or “Wye”, i. e. star connection).
• [System Para / VT] »Main VT pri« sets the nominal primary voltage Vn. Note that this•
is always the phase-to-phase voltage (independent of the connection type).
• [System Para / VT] »Main VT sec« sets the nominal secondary voltage Vn. Note that•
this is always the phase-to-phase voltage V LL (independent of the connection type).
76 www.eaton.com E-Series Family Quick Start Guide
5 Conguration via PowerPort-E
5.2.4 Relay Outputs (Binary Outputs)