Unused Setting Token
Operational
Info
Ack/Rst
Ok
CTRL
ℹ Acknowledgment signal for the LED. If latching is set to active the LED can only be acknowledged if all signals that initiated the setting of the LED are no longer present.
Ack signal
-.-
Latched Inactive
Ack signal - . -
LED Active Color Red
LED Inactive Color -
Assignment 1 50P[1] . Active
Inverting 1 Inactive
Assignment 2 - . -
Inverting 2 Inactive
Assignment 3 - . -
Inverting 3 Inactive
Assignment 4 - . -
Inverting 4 Inactive
Assignment 5 - . -
Inverting 5 Inactive
Name Value
Device Para/LEDs/LEDs group A/LED 1]
The circled dash “⊝” token indicates a
parameter that is currently not used or not
relevant.
In the example shown left, the LED is set to be
non-latching: »Latched« = “Inactive”. Therefore
it does not make sense to have a setting for the
acknowledgment (reset) of this LED, so that the
parameter »Ack signal« is marked as irrelevant.
54 www.eaton.com E-Series Family Quick Start Guide
3 Quick Start – Operation via Panel
3.11 Assisting Tokens