For example, if the digital input number 1 of slot number 1 receives an “active” signal as
soon as the switchgear is in “ON” position, then set »CinBkr-52a« = “DI Slot X1 . DI 1”.
And if the digital input number 2 of slot number 1 receives an “active” signal as soon as the
switchgear is in “OFF” position, then set »CinBkr-52b« = “DI Slot X1 . DI 2”.
These inputs “Aux ON” and “Aux OFF” are monitored also with respect to time: If it takes a
switchgear device more time to operate than is acceptable (or if the “Aux ON/OFF” signals
contradict each other) then the protection device assumes that it is disturbed. (This is
signaled via the output signal [Operation / Status Display / Control / Qx] »Pos Disturb«.)
Of course, the protection device needs to know for each switchgear devices what the
acceptable times are.
For every switchgear device “Qx”, enter the menu branch [Control / Bkr / Qx / General
Settings] and set the time »t-Move CLOSE« to move to the ON position, and the time »t-Move
OPEN« to move to the OFF position.
Have a look at the other settings in the menu branch [Control / Bkr / Qx / General Settings],
too. Depending on the switchgear type it can be necessary to set these as well.