EMR-4000 IM02602009E
Parameter Description Setting range Default Menu path
Start P Demand Fc Start of the calculation, if the assigned signal becomes
true.
Only available if: Start P Demand via: = StartFct
1..n, Assignment
List
-.- [Device Para
/Statistics
/Demand
/Power Demand]
ResFc P Demand Resetting of Statistics - Power Demand (avg, peak avg) 1..n, Assignment
List
-.- [Device Para
/Statistics
/Demand
/Power Demand]
Duration P Demand Recording time
Only available if: Start P Demand via: = Duration
2 s,
5 s,
10 s,
15 s,
30 s,
1 min,
5 min,
10 min,
15 min,
30 min,
1 h,
2 h,
6 h,
12 h,
1 d,
2 d,
5 d,
7 d,
10 d,
30 d
15 s [Device Para
/Statistics
/Demand
/Power Demand]
Window P Demand Window configuration Sliding,
Fixed
Sliding [Device Para
/Statistics
/Demand
/Power Demand]