EMR-4000 IM02602009E
Resets
Collective Acknowledgments for Latched Signals:
Collective Acknowledgments
LEDs Relay Outputs SCADA Pending
Trip Command
LEDs+
Relay Outputs+
SCADA+
Pending
Trip Command
Via PowerPort-E
or at the
panel
all...
can be
acknowledged.
At the panel, the
[Operation\
Acknowledge]
menu can directly
be accessed via
the »C« key.
All LEDs at once:
Where?
[Operation\
Acknowledge]
All Relay Outputs
at once:
Where?
[Operation\
Acknowledge]
All SCADA signals
at once:
Where?
[Operation\
Acknowledge]
All pending trip
commands at
once:
Where?
[Operation\
Acknowledge]
All at once:
Where?
[Operation\
Acknowledge]
External
Acknowledg-
ment*:
Via a signal from
the assignment
list (e.g.: a digital
Input)
all
... can be
acknowledged.
All LEDs at once:
Where?
Within the
Ex Acknowledge
menu.
All Relay Outputs
at once:
Where?
Within the
Ex Acknowledge
menu.
All SCADA signals
at once:
Where?
Within the
Ex Acknowledge
menu.
All Pending Trip
commands at
once:
Where?
Within the
Ex Acknowledge
menu.
All at once:
Where?
Within the
Ex Acknowledge
menu.
*The External Acknowledgement might be disabled if parameter »
Ex Acknowledgement«
is set to »
inactive«
within
menu [Device Para/Ex Acknowledge]. This blocks also the acknowledgement via Communication (e.g. Modbus).
www.eaton.com 195