EMR-4000 IM02602009E
Zone Interlocking
Only for Zone Interlock Tripping Outputs (Zone Interlock, semiconductor
output): 5 Vdc, <2mA for connection to electronic inputs only.
Zone Out:
Output voltage (High) 4.75 to 5.25 Vdc
Output voltage (Low) 0.0 to +0.5 Vdc
Zone In:
Nominal input voltage +5 Vdc
Max. input voltage +5.5 Vdc
Switching threshold ON min. 4.0 Vdc
Switching threshold OFF max. 1.5 Vdc
Galvanic isolation 2.5 kV ac (to ground and other IO)
Connection: Screw-type terminals (twisted pair)