EasyManua.ls Logo

Eaton EMR-4000 - Breaker Wear

Eaton EMR-4000
998 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EMR-4000 IM02602009E
Breaker Wear
The protective relay offers the following Breaker Wear features:
Monitoring of the accumulated interrupted currents.
Slow breaker alarm
Calculation of the Breaker Open Capacity »
Bkr OPEN capacity«
. 100% means that breaker maintenance is
mandatory now.
Breaker Wear Curve
Monitoring of total CLOSE/OPEN cycles and alarm for max allowed CLOSE/OPEN cycles per hour.
Slow Breaker Alarm
An increase of the closing or opening time of the breaker is an indication for the maintenance need of this switchgear. If
the measured time exceeds the time »
t-Move OPEN«
or »
t-Move CLOSE«,
the signal »BWEAR SLOW BREAKER« will be
activated. This signal will be active until it is reset manually.
www.eaton.com 401

Table of Contents

Related product manuals