EasyManua.ls Logo

Eaton EMR-4000 - Decommissioning - Removing the Plug from the Relay

Eaton EMR-4000
998 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EMR-4000 IM02602009E
Decommissioning Removing the Plug from the Relay
Dismounting the relay will lead to a loss of the protection functionality. Ensure
that there is a back-up protection. If you are not aware of the consequences of
decommissioning the device – STOP! DO NOT start.
Inform SCADA before you start.
Switch-off the power supply.
Ensure that the cabinet is de-energized and that there are no voltages that
could lead to injury of personnel.
Disconnect the terminals at the rear-side of the device. DO NOT pull any cable
pull on the plug! If it is stuck, use a screw driver.
Fasten the cables and terminals in the cabinet by means of cable clips to
ensure that no accidental electrical connections are caused.
Hold the device at the front-side while removing the mounting nuts.
Remove the device carefully from the cabinet.
In case no other device is to be mounted or replaced, cover/close the cut-out in
the front-door.
Close the cabinet.
www.eaton.com 839

Table of Contents

Related product manuals