EMR-4000 IM02602009E
Options for Individual Acknowledgments for Latched Signals:
Individual Acknowledgment
LEDs Relay Output Pending
Trip Command
Via a signal from the
assignment list (e.g.: a
digital Input), a
single
... can
be acknowledged.
Single LED:
Where?
Within the Configuration
menu of this single LED.
Relay Output:
Where?
Within the Configuration
menu of this single Relay
Output.
Pending Trip Command.
Where?
Within the module
TripControl
If the User is within the parameter setting mode, the User cannot acknowledge.
In case of a fault during parameter setting via the operating panel, the User
must first leave the parameter mode by pressing either the push-buttons
»Ack/Rst« or »OK« before accessing the »Acknowledgement menu via the
push-button.