EMR-4000 IM02602009E
Parameter Description Setting range Default Menu path
Remote Reset Enables or disables the option to acknowledge from
external/remote via signals (assignments) and
Communication.
Inactive,
Active
Active [Device Para
/Ex Acknowledge]
Ack LED All acknowledgeable LEDs will be acknowledged if the
state of the assigned signal becomes true.
Only available if: Remote Reset = Active
1..n, LEDAcknList -.- [Device Para
/Ex Acknowledge]
Ack RO All acknowledgeable Relay Outputs will be acknowledged
if the state of the assigned signal becomes true.
Only available if: Remote Reset = Active
1..n, Assignment
List
-.- [Device Para
/Ex Acknowledge]
Ack Comm Communication will be acknowledged if the state of the
assigned signal becomes true.
Only available if: Remote Reset = Active
1..n, Assignment
List
-.- [Device Para
/Ex Acknowledge]
Scaling Display of the measured values as primary, secondary,
or per unit values
Per unit values,
Primary values,
Secondary values
Primary values [Operation
/General Settings]
Maint Mode Activation Mode of the Arc Flash Reduction. Switching
into another mode is only possible when no Activation
Signal is active (pending).
Inactive,
Activation Manually,
Activation via
Comm,
Activation via DI
Inactive [Service
/Maint Mode]
Maint Mode
Activated by
Activation Signal for the Arc Flash Reduction
Maintenance Switch
Only available if: Maint Mode Activated by = Activation
via DI
1..n, Dig Inputs DI-8P X1.DI 7 [Service
/Maint Mode]
Program Mode Program Mode Either Motor Stop-
ped or Running,
Motor Stop
Either Motor
Stopped or
Running
[System Para]
www.eaton.com 277